Bypass Depending on whether the bypass is energised by a valve or by a second pump, a corresponding adjust- ment can be made in the menu item Variant. De- pending on the variant, different control logics are applied: Pump: In this version, a bypass pump is placed in front of the collector pump.
Page 3
CS bypass The CS bypass function is a different possibility to ac- is exceeded for the delay time. When solar loading be- tivate the collector circuit. To enable the use of the gins or the irradiation value remains below the switch- CS bypass function, a CS10 irradiation sensor has to on value for the delay time, the relay is switched off.
Function block In addition to the pre-defi ned optional functions, func- Thermostat function ∆T function tion blocks consisting of thermostat functions, timer The relay allocated to the function block is switched The relay allocated to the function block is switched and differential functions are available.
Page 5
Arrangement / Opt. functions / Add new function... / Function block Adjustment Description Adjustment range / selection Factory setting channel Relay Relay selection system dependent system dependent Thermostat a Thermostat a Yes, No Th-a on Switch-on temperature Thermostat a -40 ... 250 °C 40 °C Th-a off Switch-off temperature Thermostat a...
Heating circuits error message is indicated. For the duration of this Summer mode is activated regardless of the outdoor temperature when the switch is operated. condition, the maximum fl ow temperature -5 K is as- sumed as set fl ow temperature. Summer temperature With the timer, the day / night operation can be ad- If Summer off or Both has been selected in the...
Page 7
room thermostats, the heating circuit pump is deac- displayed. For each day of the week there is an over- tivated and the mixer remains in its current position. view display. The display can be switched back and forth between the different days by pressing buttons Common room thermostats with potential-free out- puts can be used alternatively.
Page 8
Heating / Heating circuits / New heating circuit / Internal Adjustment channel Description Adjustment range / selection Factory setting HC pump Heating circuit pump system dependent system dependent Mixer open Relay selection mixer open system dependent system dependent Mixer closed Relay selection mixer closed system dependent system dependent...
Page 9
Chimney sweeper function Adjustment channel Description Adjustment range / selection Factory setting The chimney sweeper function can be used for ena- All days, Monday ... Sunday, Days of the week Day selection bling a quick access to measurement conditions with- Continue out menu operation for the chimney sweeper.
Page 10
Inputs In- / Outputs / Inputs A d j u s t m e n t Description Adjustment range / selection Factory setting channel S1 ... S12 Sensor input selection Switch, KTY, Pt500, RTA11-M, Type Selecting the sensor type Pt1000 Pt1000, None Offset Sensor offset...