Hydro Unit
5

Example of Hydro Unit installation

■ Example of installation for cooling and heating
• When the cooling mode is required, a 2-way valve must be installed to isolate the radiator.
A 2-way valve shoud be installed to isolate the under-floor heating if necessary.
• If the minimum flow rate cannot be secured, install a buffer tank and pump.
Please refer to page 11 for how to check the flow rate.
CAUTION
Please pay attention to the cooling temperature settings, as we cannot guarantee the damages caused by the air
humidity condensation on the radiator or under-floor heating circuit and pipeline surfaces.
11-EN
▼Fig.5-01
Strainer (40 mesh / 0.4 mm)
Drain Cock for water
Charge and Drain
Indirect Sanitary
Hot Water Cylinder
Alternative to Radiators
Under-floor Heating
(Heating Only)
[2-Way Valve Control]
– 6 –
Fan Coil Units
(Cooling or Heating)
Isolating
Ball
Valves
Diverting 3-Way
Valve for
Sanitary Hot
Water Cylinder
M
Radiators (Heating Only)
[2-Way Valve Control]
2-Way
M
Valve
Use the
2-way valve
to isolate
the heating
TTW
circuit when
in cooling
mode.
Use it when do not
2-Way
M
operate cooling.
Valve