FusionModule2000 Smart Modular Data Center
Maintenance Guide
Configuration information and fault logs may be required for handling some alarms. For details,
see
Alarm Handling
After locating the component or module for which the alarm is generated, rectify
the fault.
Figure 4-2 Troubleshooting flowchart
After an alarm is cleared, prepare a report to record the alarm handling process.
Issue 02 (2022-07-30)
NO TE
Fault Information Collection Guide .
NO TE
Common alarm references are as follows:
● Data center infrastructure alarm reference in the online help of the management system
● Alarm references in documents delivered with components
● Alarm reference in this document
● Alarm reference obtained from technical support
It is recommended that the alarm handling report consists of information about the alarm
occurrence time, location, symptom, fault locating process, alarm handling process, and
alarm prevention solutions.