Fixed power

In AUTO and SEMI-AUTO mode, the ESS supplies the amount of power configured in the set point for fixed power.
The ASC can operate as a server to an external PLC/EMS controller. The ASC receives the fixed power set point from the PLC/EMS
controller using, for example, Modbus or analogue signals.
Power
Busbar
V
I
V
NOTE
The ASC can also use the current measurement from the 4th CT to calculate the mains power.
Start sequence
1. Activate a start signal.
AUTO mode: The ESS starts automatically when you select AUTO mode.
SEMI-AUTO mode: Push the Start
breaker.
2. The ESS supplies the load configured in the set point for PV fixed power (parameter 7051).
3. If the load increases to more than the set point, the mains supplies the extra load.
Settings > Power set points > Fixed Power > Set point
Parameter
7051
OPERATOR'S MANUAL 4189341343A EN
Modbus
meter
Modbus
ASC Storage
button on the controller and then push the Close breaker
Text
Set point
PLC
Range
-20000 to 2000 kW
button to close the ESS
Default
500 kW
Page 19 of 36