Date: 08/06/2020
Subject: RAC 2.0 Common Option Settings
Models: AR**TSF*BWKNCV (RNS***BT), AR**TSF*BWKXCV (RXS****T)
RAC 2.0 Common Option Settings
Various installation option settings are available for Samsung RAC 2.0 systems to modify system operation or to utilize
features not enabled from the factory. Installation options can be modified via the included wireless remote controller, an
optional wired controller, or with the SNET Pro 2 service software (requires the use of a MIM-C02N service tool, sold
separately). Each segment or digit within the "02" installation option code represents a separate option. There are a total
of 24 segments in the installation option code - including page numbers, but not every segment is used for every model.
Below is a general description of each segment that is used for RAC 2.0 indoor units.
Programming instructions and examples can be found on page 7 of this document
Segment 3: Auto clean
The auto clean option is used to remove moisture from the evaporator coil after the indoor unit is turned off. This setting
will operate the indoor fan for 10 to 30 minutes depending on conditions to dry the evaporator coil. This helps to prevent
the buildup of mold on the evaporator coil, thus helping to eliminate odor. The end user can cancel the Auto Clean
function while it is running by pressing and holding the "Options" button on the wireless remote for 3 or more seconds.
Value
0 (default)
1
© 2020 Samsung HVAC
020000-100000-200001-300000
Auto clean
Details
Disabled
Enabled
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
www.SamsungHVAC.com TB2020-0015 (REV 12/15/2020)
TECHNICAL BULLETIN 2020-0015
1

Advertisement

loading

Summary of Contents for Samsung AR TSF BWKNCV Series

  • Page 1 RAC 2.0 Common Option Settings Various installation option settings are available for Samsung RAC 2.0 systems to modify system operation or to utilize features not enabled from the factory. Installation options can be modified via the included wireless remote controller, an optional wired controller, or with the SNET Pro 2 service software (requires the use of a MIM-C02N service tool, sold separately).
  • Page 2 Segment 5: Central controller use The central controller option is used when the system needs to be tracked and controlled by a Samsung upper level controller (DMS 2.5, BACnet/LonWorks gateways, or the central touch controller). This is enabled by default.
  • Page 3 TECHNICAL BULLETIN 2020-0015 Segment 14: External contact control input The external contact control option is used to control an indoor unit via an external dry contact. This option must also be set to use segment 15 (external contact output). Either MIM-B14 external contact control interface module, wired controller sub-PCB (purchased separately) integral CN83 pigtail, or included female plug referenced in the segment 8 section, must be used depending on the application.
  • Page 4 TECHNICAL BULLETIN 2020-0015 MIM-B14 Input MIM-B14 Feature Option Then Terminals - Unit turns OFF Contact Opens ON/OFF Control - Controller ENABLED (unit can be turned on via controller) Contact Closes - Indoor unit turns ON in previous mode - Unit turns OFF Contact Opens - Controller DISABLED (unit cannot be turned on via controller) OFF-Only...
  • Page 5 TECHNICAL BULLETIN 2020-0015 Segment 17: Use of chime The indoor unit chime can be disabled with this option. The wireless remote can also be used to enable/disable the chime. The indoor unit option setting has priority over the wireless remote setting. Use of chime Value Details...
  • Page 6 TECHNICAL BULLETIN 2020-0015 Segment 20: Individual control of wireless controller (channel setting) The indoor unit can be set to a specific channel or zone (1 - 4) for wireless remote controller use. This option is used when multiple indoor units are in the same space and prevents an indoor unit from accepting the wireless signal if it is not programmed to the same channel as the wireless controller.
  • Page 7 TECHNICAL BULLETIN 2020-0015 Indoor unit programming with wireless controller (single option setting method) segment number single option installation option (ones digit) setting mode setting mode Press Press segment number option setting (tens digit) 1. Remove the batteries and wait for the screen to go blank. While holding the temperature up and down buttons, replace the batteries.

This manual is also suitable for:

Ar tsf bwkxcv seriesRns bt seriesRxs t series