York YCAS Series Wiring Diagram page 8

Air-cooled screw liquid chillers
Table of Contents

Advertisement

OPTIONAL SINGLE-POINT POWER SUPPLY WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS –
(One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (standard) or Non-Fused Disconnect (option).
Chiller
Model
Volts
MRA
1
YCAS
(MCA)
Disc Sw.
0373
380
296
0403
380
321
0453
380
375
0503
380
430
0543
380
387
0573
380
455
0623
380
493
0653
380
464
See page 4 for Electrical Data footnotes.
8
ELECTRICAL DATA (CONT'D)
LD05549
2 COMPRESSOR UNITS
Individual System Circuit Breakers in each Motor Control Center
Field Provided Power Supply
Min. NF
Over-Current Protection
2, 9
Min.
3, 5
Max.
400
300
350
400
350
400
400
400
450
600
450
500
400
400
450
600
500
500
600
500
600
600
500
500
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION AND INDIVIDUAL SYSTEM CIRCUIT
BREAKERS
Suitable for:
Y - ∆ Start and
Across-The-Line-Start
One fi eld provided power supply circuit to the unit.
Field con nec tions to factory pro vid ed Non-Fused
Dis con nect Switch (Opt), or Terminal Block (Opt).
Factory con nec tions to Circuit Breakers on Ter mi nal
Blocks in each of the two Power Panels.
See page 4 for notes.
)
10
FIELD-SUPPLIED WIRING
Factory Provided (Lugs) Wire Range
13
Standard
4, 6
Terminal Block
2/0 - 500
(2) 1/0 - 300
(2) 1/0 - 300
(2) 2/0 - 500
(2) 1/0 - 300
(2) 2/0 - 500
(2) 2/0 - 500
(2) 2/0 - 500
FORM 201.19-W3 (1104)
7
Optional NF
Disc. Switch
(2) 3/0-250
(2) 3/0-250
(2) 3/0-250
(2) 250-500
(2) 3/0-250
(2) 250-500
(2) 250-500
(2) 250-500