York YCAS Series Wiring Diagram page 13

Air-cooled screw liquid chillers
Table of Contents

Advertisement

COMPRESSOR DATA
VOLTAGE CODE-
MAX kW
MAX AMPS
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMERS)
NO. OF
COMPRESSORS
2
CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF
COMPRESSORS
2
YORK INTERNATIONAL
ELECTRICAL DATA (CONT'D)
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA – MOTOR CODE A
(B5N, B5E, B6N, B6E)
50
113
193
CONTROL
POWER
SUPPLY
115V-1Ø
CONTROL
POWER
SUPPLY
400V - 50 HZ
DXS36LA – MOTOR CODE A
(A5N, A5E, A6N, A6E)
50
113
193
MCA
MAX DUAL
(MAX LOAD
ELEMENT
CURRENT)
FUSE SIZE
20A
MCA
RECOMMENDED
(MAX LOAD
DUAL ELEMENT
CURRENT)
FUSE SIZE
6.3A
FORM 201.19-W3 (1104)
DXS24LA – MOTOR CODE (TBD)
(C5N, C5E, C6N, C6E)
50
80
135
NON-FUSED
DISCONNECT
SWITCH SIZE
20A
30A
NON-FUSED
DISCONNECT
SWITCH SIZE
15A
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents