York YCAS Series Wiring Diagram page 7

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Model
Volts
MRA
Min. NF
1
YCAS
(MCA) Disc. Sw.
2,9
0373
380
148
150
0403
380
160
200
0453
380
188
200
0503
380
215
250
0543
380
193
200
0573
380
227
250
0623
380
247
250
0653
380
232
250
YORK INTERNATIONAL
ELECTRICAL DATA
SYSTEM #2 FIELD-SUPPLIED WIRING
Over-current
Factory Provided (Lugs) Wire Range
Protection
13
Std. Terminal
Min.
Max.
3, 5
4, 6
Block
200
250
# 2 - 4/0
200
250
# 2 - 4/0
225
300
1/0 - 300
300
350
1/0 - 500
250
300
1/0 - 300
300
350
2/0 - 500
300
400
2/0 - 500
300
350
2/0 - 500
7
Optional NF.
Optional
Disc. Sw.
Circuit Breaker
# 4 - 300
# 6 - 350
# 4 - 300
# 6 - 350
# 6 - 350
# 6 - 350
# 6 - 350
(2) 3/0-250
# 6 - 350
# 6 - 350
# 6 - 350
(2) 3/0-250
# 6 - 350
(2) 3/0-250
# 6 - 350
(2) 3/0-250
FORM 201.19-W3 (1104)
Compressor
Fans
11, 12
FLA
LRA
RLA Y-LRA
X-LRA Qty.
(Ea.) (Ea.)
108
241
761
3
4.4
17.1
118
241
761
3
4.4
17.1
140
309
979
3
4.4
17.1
161
309
979
3
4.4
17.1
141
309
979
4
4.4
17.1
168
309
979
4
4.4
17.1
183
309
979
4
4.4
17.1
168
309
979
5
4.4
17.1
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents