To perform an insulation check of the compressor
RXQ25+35AMV1B + ARXQ25+35AMV1B + FTXQ25+35AMV1B +
ATXQ25+35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
Compressor motor winding current
measurements are correct?
Yes
No
Prerequisite: First perform an electrical check of the compressor, see
"3.2.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Wait until the rectifier voltage is below 10 V DC.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
Action
Perform an insulation check of the
compressor, see
procedures" [
Preventively replace the compressor,
see
"3.2.2 Repair
4
 50].
3
Components
|
"3.2.1 Checking
4
 50].
4
procedures" [
 56].