Light Emitting Diode (Led) - Siemens Reyrolle 7SR46 Manual

Hide thumbs Also See for Reyrolle 7SR46:
Table of Contents

Advertisement

Device Functionality
2.1 Front Fascia
Keys

Light Emitting Diode (LED)

2.1.4
Indication LEDs
The 7SR46 Argus relay provides 2 non-programmable LEDs and 2 user-programmable LEDs.
The LED functions are:
Table 2-1
LEDs
Parameters
LED 1
HEALTHY
LED 2
O/C
LED 3
E/F
LED 4
LOW BATTERY
Healthy LED
The steady illumination of Protection HEALTHY LED indicates that the required CT current 0.8 ⋅ I
or 0.4 ⋅ I
(3-phase) or auxiliary power supply is applied to the relay, which indicates a healthy relay.
smin
Low Battery LED
The low battery LED indicates when the battery voltage falls below the operating voltage.
User-Programmable LEDs
The 7SR46 Argus relay consists of 2 user-programmable LEDs which can be configured to protection functions
and miscellaneous functions. The LEDs (L2, L3) are programmed to be illuminated as RED.
User-Programmable LED Configuration
The 2 user-programmable LEDs are assigned to any functions by navigating OUTPUT CONFIG > OUTPUT
MATRIX menu.
1
Default factory setting and can be programmed as per user requirements.
18
Description
This push-button is used to return the relay display to its initial status or one
level up in the menu structure. Press CANCEL to return to the previous menu
or to cancel the value.
This push-button is used to reject any alterations to a setting while in the edit
mode.
Press the CANCEL key repeatedly to return to the Relay Identifier screen.
This push-button is used to power on and power off the relay with battery
power when the auxiliary power, CT power, and USB power are not available.
This push-button is used to turn on and turn off the backlight.
LED Functions
Indication Color
Green
Red
1
Red
1
Amber (continuous) Indicates when the battery voltage is less than
Amber (blinks)
Functions
Indicates the relay protection function in a
healthy state
LEDs L2 to L3 are user-programmable LEDs. They
indicate when the respective mapped function is
triggered.
By default, these LEDs are mapped to O/C (phase
overcurrent) and E/F (earth fault) functions.
the operating level
Critical battery condition
Reyrolle, 7SR46 Device, Manual
C53000-G7040-C103-1, Edition 10.2022
(1-phase)
smin

Advertisement

Table of Contents
loading

Table of Contents