8 Servicing/Maintenance
CAUTION
Strong magnetic field in the pump rotor area
Interference with magnetic data carriers, electronic devices, components and
instruments!
Uncontrolled magnetic attraction forces between magnetic components, tools or
similar!
▷ The rotor must generally be removed from the electronic system housing by
authorised specialist personnel only.
▷ Remove any magnetic parts from the vicinity of the pump rotor.
▷ Keep the assembly area clean.
CAUTION
Strong magnetic field
Negative impact on or damage to electrical devices!
▷ The pump rotor must be removed from the electronic system housing by
authorised specialist personnel only.
ü The pump set has been de-energised and secured against unintentional start-up.
ü The pump has cooled down to ambient temperature.
ü A container for collecting the fluid has been positioned underneath the pump
set.
1. Close the shut-off elements.
2. Disconnect the discharge nozzle and suction nozzle from the piping.
3. Depending on the pump size / motor size, remove the supports from the pump
set.
4. Remove the complete pump set from the piping.
Calio SI Dual / Calio SI Therm
43 of 50