ZONEBB3Z(AC/HP)01: Quick Reference Guide
NOTE: ZONEBB3ZAC01 model does
not have HPT connector.
Fig. 6 – Leaving Air Temperature (LAT) Sensor
Please refer to Limit Temperature Levels and Actions Table in the
Installation and Start-Up Instructions for additional information on the
response of the system to LAT/HPT sensors.
Step 6 – Connect the Power Supply
Optional: Use a dedicated 24 VAC, 40 VA, 60 Hz isolated transformer
(not included).
Otherwise, if the cooling and heating systems have separate
transformers, twist off the Rc/Rh jumper using a pair of long nosed
pliers. Then connect the R of the cooling transformer to Rc, the R of the
heating transformer to Rh and the common of both transformers to C.
Connect a jumper wire between Rz and Rc. Rc powers G,Y, and O
outputs. Rh power W outputs.
Dipswitch
Operation Description
Position
Auto changeover time between heating and
1
cooling or vice versa
Together with dipswitch 3, determines
2
chanegover time
3
Multiplier for the modified time set on dipswitch 2
Installer Test Mode used to check system
4
operation
Disables zoning operation with all dampers open
5
and Zone 1 thermostat as controller
6
Setting G (Fan) to energize with W
7
Sets Leaving air Temperature (LAT) limit
temperature (HP/2 Stage control only)
8
Designated Zoning Controller connection to heat
9
pump (HP) or an air conditioner (AC)
Designates the type of thermostat used with the
10
Zoning Controller (HP or AC)
Disable over/under temperature protection for the
11
equipment in emergency situations
Determine the Reversing Valve is energized for
12
cooling (O function) or heating (B function)
*. For 2 stage heating, the stat may be a 2 stage heat AC stat or a HP stat converted to AC.
†. Uses an AC stat with 2 stage heating instead of a HP stat.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Step 7 – Wire the HVAC Equipment
The descriptions below and
wiring diagram for your system.
dipswitches 9 and 10 for each diagram.
There are 8 dipswitch settings on the AC zone control and an additional
4 dipswitch on the HP zone controls board.
function and available settings.
Table 1 – Dipswitch Settings
Default (OFF)
Auto changeover time
ENABLED (OFF)
20 minutes auto changeover
time (OFF)
1.0 multiplier (OFF)
Normal operation (OFF)
Zoning Operation ENABLED
(OFF)
W NOT energized with G (OFF)
145°F
(OFF)
1 or 2 Speed HP / 1 Stage Aux.
Heat (OFF)
LAT and HPT Safety Protection
ENABLED (OFF)
Reversing Valve energized on

COOLING (OFF)

4
Fig. 7 – Connecting the Power Supply
Table 1
will help you choose the connect
Table 1
also shows the proper setting of
Table 1
Fig. 8 – Dip Switches
Optional Settings
Auto changeover time DISABLED
30 minutes auto changeover time (ON)
0.5 multiplier (ON)
Installer Test Mode ENABLED (ON)
Zoning Operation DISABLED (ON)
W energized with G (ON)
160°F
(OFF)
(ON)
130°F
(OFF)
(ON)
1 or 2 Speed
1 Speed HP / 1
AC / 1 or 2
Stage Aux
*
Stage Heat
Heat
(ON)
LAT and HPT Safety Protection DISABLED (ON)
Reversing Valve energized on HEATING (ON)
summarizes their
175°F
(ON)
(OFF)
(ON)