Download Print this page

Temperature Rise Data - Trane Precedent FIAEHTB309 Series Installation Instructions Manual

Packaged rooftop units 6 to 25 tons - standard efficiency

Advertisement

Temperature Rise Data

Table 4.
Air temperature rise
6 Tons
kW
Stages
1800 cfm
9.00
1
15.81
18.00
1
31.61
27.00
2
47.42
36.00
2
63.22
54.00
2
72.00
2
(a) For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula:
Temp. rise across Electric Heater = (kW x 3414)/(1.08 x cfm).
14
(a)
7.5 Tons
8.5 Tons
10 Tons
2250 cfm
2550 cfm
3000 cfm
12.64
11.16
25.29
22.31
37.93
33.47
50.58
44.63
12.5 Tons
15 Tons
3750 cfm
4500 cfm
18.97
15.17
12.64
28.45
22.76
37.93
30.35
25.28
56.90
45.52
37.93
17.5 Tons
20 Tons
25 Tons
5250 cfm
6000 cfm
7500 cfm
21.67
18.96
32.51
28.45
43.35
37.93
ACC-SVN228B-EN
15.17
22.76
30.34

Hide quick links:

Advertisement

loading