iSMA-B-MINI/MIX BACnet User Manual Table of Contents Introduction ..........................6 Revision History..........................7 Safety Rules..........................10 Wiring............................... 11 EN 60730-1 Power Supply Considerations ................11 FCC Compliance Note........................11 Technical Specification ......................13 Summary Table for All Modules ....................16 Hardware Specification ....................... 18 Dimensions ............................
Page 3
iSMA-B-MINI/MIX BACnet User Manual 5.3.1 Digital Input Counter ......................31 Analog Outputs ..........................31 5.4.1 Analog Output Voltage Connection ................... 31 5.4.2 Analog Output Relay Connection ..................32 5.4.3 Analog Output Actuator Connection ................. 32 Digital Outputs ..........................32 5.5.1 Digital Output Solenoid Valve Connection ...............
Page 4
iSMA-B-MINI/MIX BACnet User Manual 8.2.1 BI - Digital Input Object Description (Binary Input: 0-11)..........46 8.2.2 BIA COUNTER Object (Accumulator: 0-12) ............... 47 8.2.3 BI COUNTER Object (Analog Value: 2-13) ................. 47 Analog Output BACnet Objects....................48 8.3.1 AO - Analog Output Object Description (Analog Output: 0-5)........48 8.3.2 AO CONFIGURATION Object (Multistate Value: 17-22) ..........
Page 5
iSMA-B-MINI/MIX BACnet User Manual List of Supported Temperature Sensors ................ 80 www.ismacontrolli.com DMP261en | 1st Issue rev. 8 | 05/2022 page 5 of 114...
iSMA-B-MINI/MIX BACnet User Manual 1 Introduction The MINI and MIX series of I/O modules with RS485 and IP (2 Ethernet) have been designed for building distributed control systems using MAC36, AAC20, or another controller. Each module is equipped with the most commonly used types of I/O in building automation.
iSMA-B-MINI/MIX BACnet User Manual 1.1 Revision History Rev. Date Description 28 Aug 2015 First edition 1 Feb 2016 • Information about the capacitive load relay added to the technical specifications. • Information about load triac outputs added to the technical specifications.
Page 8
iSMA-B-MINI/MIX BACnet User Manual Rev. Date Description • I/O watchdog reset after read/write registers through USB modified; • Sensors added for the immediate detection of short circuit and disconnection, regardless of filter settings on universal inputs; • Fixed bug with Stop bits, it was always 1. 16 May 2017 •...
Page 9
iSMA-B-MINI/MIX BACnet User Manual Rev. Date Description 25 May 2022 Rebranded Table 1. Revision history www.ismacontrolli.com DMP261en | 1st Issue rev. 8 | 05/2022 page 9 of 114...
iSMA-B-MINI/MIX BACnet User Manual 2 Safety Rules • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on. • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
iSMA-B-MINI/MIX BACnet User Manual 2.1 Wiring In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module.
Page 12
iSMA-B-MINI/MIX BACnet User Manual particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: •...
iSMA-B-MINI/MIX BACnet User Manual 3 Technical Specification Power supply Voltage 24 V AC/DC ± 20% Power consumption Module type At 24 V DC At 24 V AC 0.4 W 0.6 VA 8I-IP 1.4 W 2.1 VA 0.5 W 0.8 VA 8U-IP 1.5 W 2.3 VA...
Page 14
iSMA-B-MINI/MIX BACnet User Manual Current input Current measurement in 0 - 20 mA range Required external resistor 200 Ω Measurement accuracy ±1.1% Measurement resolution 15 µA at 12-bit and 5 µA at 16- Resistive input Measurement of resistance in 0 to 1000 kΩ range Measurement resolution for 20 kΩ...
Page 15
iSMA-B-MINI/MIX BACnet User Manual Digital Outputs Contact material AgSnO2 (relays) UL compliant ratings Maximum ratings 4O-H and 4O-H-IP Resistive load AC1 8 A at 230 V AC 8 A at 230 V AC 8 A at 30 V DC 8 A at 30 V DC Inductive load AC3 37 VA at 230 V AC...
iSMA-B-MINI/MIX BACnet User Manual Humidity Relative 5% to 95% Connectors Type Removable Maximum cable size 2.5 mm (18–12 AWG) Maximum tightening torque 0.35 Nm Dimensions MIX18, MIX18-IP Width 110 mm (4.331 in) Length 88 mm (3.4646 in) Height 62 mm (2.441 in) MIX38, MIX38-IP Width 110 mm (4.331 in)
iSMA-B-MINI/MIX BACnet User Manual 4 Hardware Specification 4.1 Dimensions 4.1.1 MINI Series Dimensions Figure 2. The MINI series dimensions 4.1.2 MIX18 Series Dimensions Figure 3. The MIX18 series dimensions 4.1.3 MIX38 Series Dimensions Figure 4. The MIX38 series dimensions www.ismacontrolli.com DMP261en | 1st Issue rev.
iSMA-B-MINI/MIX BACnet User Manual 4.2 Power Supply Connection Figure 5. AC power supply connection Figure 6. DC power supply connection 4.3 LED Indicators 4.3.1 MIX Series Front Panels MIX18 Top Panels Figure 7. The MIX18 top panel Figure 8. The MIX18-IP top panel www.ismacontrolli.com DMP261en | 1st Issue rev.
iSMA-B-MINI/MIX BACnet User Manual MIX38 Top Panels Figure 9. The MIX38 top panel Figure 10. The MIX38-IP top panel 4.3.2 MINI Series Front Panels MINI 8I and 8I-IP Top Panels Figure 11. The 8I top panel Figure 12. The 8I-IP top panel The MINI 8U and 8U-IP Top Panels Figure 13.
Page 21
iSMA-B-MINI/MIX BACnet User Manual The MINI 4I4O-H and 4I4O-H-IP Top Panels Figure 15. The 4I4O-H top panel Figure 16. The 4I4O-H-IP top panel The MINI 4U4O-H and 4U4O-H-IP Top Panels Figure 17. The 4U4O-H top panel Figure 18. The 4U4O-H-IP top panel The MINI 4U4A-H and 4U4A-H-IP Top Panels Figure 19.
Page 22
iSMA-B-MINI/MIX BACnet User Manual The MINI 4O-H and 4O-H-IP Top Panels Figure 21. The 4O-H top panel Figure 22. The 4O-H-IP top panel The MINI 4TO-H and 4TO-H-IP Top Panels Figure 23. The 4TO-H top panel Figure 24. The 4TO-H-IP top panel •...
iSMA-B-MINI/MIX BACnet User Manual 4.4 RS485 Port 4.4.1 RS485 Communication Bus Connection Figure 25. RS485 connection 4.4.2 RS485 Network Termination Transmission line effects often present problems for data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends with a resistor across the line adequate to its characteristic impedance.
Device ID = Vendor ID * 1000 + MAC + 128 (only in BACnet slave) where iSMA CONTROLLI Poland Vendor ID = 826. For example, if the MAC address is set to 41, and the protocol is set to BACnet master, then the Device ID = 826041, or if the protocol is set to BACnet slave, then the Device ID = 826169.
iSMA-B-MINI/MIX BACnet User Manual Baud Rate Off (0) Off (0) Off (0) Defined by the user in the register Off (0) Off (0) On (1) 76800 Off (0) On (1) Off (0) 4800 Off (0) On (1) On (1) 9600 On (1) Off (0) Off (0)
Page 26
iSMA-B-MINI/MIX BACnet User Manual DATA BITS PARITY BITS RESPONSE DELAY WATCHDOG TIME 0 (disabled) DEFAULT STATE OF DIGITAL OUTPUTS (1-12) DEFAULT STATE OF THE ANALOG OUTPUTS (DIGITAL 1-6) DEFAULT STATE OF THE ANALOG OUTPUTS (1-6) UNIVERSAL INPUT CONFIGURATION (1-8) INPUT FILTER TIME CONSTANT (1-8) UNIVERSAL INPUT RESOLUTION (1-8) ANALOG OUTPUT CONFIGURATION (1-6) COV INCREMENT (BACnet only)
iSMA-B-MINI/MIX BACnet User Manual 4.8.1 Restoring Default Settings To restore the default configuration of all registers, follow the steps below: • turn off the power supply; • set section 6 of the S3 switch to on; • turn on the power supply, the power LED will start blinking; •...
iSMA-B-MINI/MIX BACnet User Manual 5 Inputs and Outputs 5.1 Local I/O The iSMA-B-MINI/MIX modules are equipped with local inputs and outputs (universal inputs, digital inputs, analog outputs, digital outputs, and triac outputs), and their quantities differ between the modules types, according to the table: Module Type 4I4O-H ...
iSMA-B-MINI/MIX BACnet User Manual • resistance and temperature measurement (10k thermistor, a full list of supported temperature sensors is available here: List of Supported Temperature Sensors); • dry contact (output current 1 mA). Current measurement is realized by voltage measurement and 200 Ω resistance. According to Ohm’s law, the current is directly proportional to the voltage, and the resistance is the constant of proportionality.
iSMA-B-MINI/MIX BACnet User Manual 5.2.3 Universal Input Resistance Connection Figure 30. A universal input resistance connection 5.2.4 Universal Input Dry Contact Connection Figure 31. A universal input dry contact connection 5.3 Digital Inputs Digital inputs operate as standard dry contact inputs and, additionally, as high speed pulse counters up to 100 Hz.
iSMA-B-MINI/MIX BACnet User Manual Figure 32. A digital input connection 5.3.1 Digital Input Counter A digital input can work as a counter of dry contact pulses up to 100 Hz. The connection is identical as in case of the dry contact input. 5.4 Analog Outputs Analog outputs provide a 0-10 V DC output with maximum load up to 20 mA.
iSMA-B-MINI/MIX BACnet User Manual 5.4.2 Analog Output Relay Connection Figure 34. An analog output relay connection 5.4.3 Analog Output Actuator Connection Figure 35. An analog output actuator connection 5.5 Digital Outputs Digital outputs operate as relay outputs with maximum loads of: •...
iSMA-B-MINI/MIX BACnet User Manual 6 Conformance Statement WARNING! Changing the parameters regarding the configuration of the transmission will only take effect after restarting the unit (except for the registers the value of which is read from the switch). 6.1 Conformance Statement Regarding Implementation of BACnet Protocol Date 2020-09-04...
iSMA-B-MINI/MIX BACnet User Manual 6.1.2 Supported BACnet Interoperability Building Blocks Application Service (B-SS) Designation Data Sharing - Read Property – B DS-RP-B Data Sharing - Write Property - B DS-WP-B Data Sharing - COV - B DS-COV-B Device Management - Dynamic Device Binding - B DM-DDB-B Device Management - Dynamic Object Binding - B DM-DOB-B...
iSMA-B-MINI/MIX BACnet User Manual 7 Device Objects 7.1 Device BACnet Object Description Dynamically creatable: no, dynamically deletable: no. Property Name Require Proprieta Writabl Property Data Description Type OBJECT_IDENTIFIER OBJECT_NAME OBJECT_TYPE SYSTEM_STATUS VENDOR_NAME VENDOR_IDENTIFIE MODEL_NAME FIRMWARE_REVISIO APPLICATION_SOFT WARE_VERSION PROTOCOL_VERSIO PROTOCOL_REVISI PROTOCOL_SERVIC ES_SUPPORTED PROTOCOL_OBJECT _TYPES_SUPPORTE...
Page 39
iSMA-B-MINI/MIX BACnet User Manual Property Name Require Proprieta Writabl Property Data Description Type MAX_MASTER MAX_INFO_FRAMES DEVICE_ADDRESS_B INDING DATABASE_REVISIO ACTIVE COV SUBSCRIPTION HW_VERSION 3020 Unsigned VERSION_TYPE 3030 Unsigned RS485_BIASING 3045 Unsigned MINI IP modules only with HW_VERSION>=2.0 BAUD_RATE 3084 Unsigned USER_BAUD_RATE 3085 Unsigned IP_ADDRESS...
iSMA-B-MINI/MIX BACnet User Manual 7.2 VALID_FRAMES_FOR_US_CNT Property 5101 The property contains the number of valid frames (on the MS/TP layer) addressed to this module. 7.3 VALID_FRAMES_FOR_NOT_US_CNT Property 5102 The property contains the number of valid frames (on the MS/TP layer), which are not addressed to this module.
Page 41
iSMA-B-MINI/MIX BACnet User Manual Value Type (0x5E 8U-IP (0x53 4I4O-H (0x5D 4I4O-H-IP (0x55 4U4O-H (0x5F 4U4O-H-IP (0x56 4U4A-H (0x60 4U4A-H-IP (0x52 4O-H (0x5C 4O-H-IP (0x57 4TO-H (0x61 4TO-H-IP (0x32 MIX18 (0x33 MIX38 (0x34 MIX18-IP (0x35 MIX38-IP Table 13. Module type value assignement The high byte contains a module firmware version multiplied by 10.
iSMA-B-MINI/MIX BACnet User Manual 7.9 RS485_BIASING Property 3045 The property allows activating RS485 biasing resistors in order to pull up voltage on the RS485 bus. The function is only available in MINI IP modules with a hardware version >= 2.0. MIX IP modules with hardware version 3.0 and up have a hardware switch for RS485 biasing under the bottom cover.
iSMA-B-MINI/MIX BACnet User Manual 8 LocalIO Objects The following sections describe the BACnet objects dedicated to inputs and outputs of the iSMA-B-MINI/MIX modules. 8.1 Universal Input BACnet Objects 8.1.1 UI - Universal Input Object Description (Analog Input: 0-7) Each universal input in all types of modules is represented on the BACnet network as the BACnet Analog Input object with the following properties: Dynamically creatable: no, dynamically deletable: no.
iSMA-B-MINI/MIX BACnet User Manual Note: Object’s additional properties are saved to keep the backward compatibility with the older firmware version. In the new firmware version, each property has a corresponding BACnet object. PRESENT_VALUE and UNITS Property The property contains the actual value and unit of the universal input according to the INPUT_TYPE property value.
iSMA-B-MINI/MIX BACnet User Manual Object Description Unit Property The temperature sensor 30K6A1 NTC B=4262K °C The temperature sensor SIE1 °C The temperature sensor TAC1 °C The temperature sensor SAT1 °C The temperature sensor Pt1000 °C The temperature sensor Ni1000 °C The temperature sensor NI1000 21C °C The temperature sensor NI1000 LG...
iSMA-B-MINI/MIX BACnet User Manual WARNING! Setting the 16-bit resolution increases the measurement time for one channel from 10 ms to 140 ms. The total time necessary to measure all the channels increases from 80 ms to 1120 ms. The parameter is also available as the BACnet UI Analog Input object property number 4002.
iSMA-B-MINI/MIX BACnet User Manual Property Required Proprietary Writeable Property ID Data Type Description Name OUT_OF_SERVIC OUT OF SERVICE property POLARITY UNITS 3001 Unsigned COUNTER Table 18. Properties of the Binary Input object Note: Object’s additional properties are saved to maintain the backwards compatibility with the older firmware version.
iSMA-B-MINI/MIX BACnet User Manual type object, therefore additional objects have been created for the counters. The Analog Value has one drawback–odd values above 16777216 are rounded down by 1. For example, 16777216 + 1 is still displayed as 16777216, but 16777216 + 2 is displayed properly as 16777218.
iSMA-B-MINI/MIX BACnet User Manual Note: Additional properties of the object are saved to maintain the backward compatibility with the older firmware version. In the new firmware version, each of the properties has a corresponding BACnet object. PRESENT_VALUE Property The property contains the voltage value, expressed in mV or percentage, of the analog output PWM duty cycle.
iSMA-B-MINI/MIX BACnet User Manual Object Value Description Unit Property PWM 1 Hz PWM 10 Hz PWM 100 Hz PWM 0.1 HZ PWM 0.01 Hz Table 21. The AO Configuration object value list This configuration is also available in the AO Analog Output object as the OUTPUT_TYPE property 4001.
Page 51
iSMA-B-MINI/MIX BACnet User Manual Property Required Proprietary Writable Property ID Data Type Description Name OBJECT_IDENTIFI From BO:0 to BO:12 OBJECT_NAME BO-x OBJECT_TYPE PRESENT_VALUE PRESENT_VALUE property STATUS_FLAGS STATUS FLAG property EVENT_STATE OUT_OF_SERVIC OUT OF SERVICE property POLARITY PRIORITY_ARRAY RELINQUISH_DE FAULT 3014 Enumerated HAND_STATUS Table 23.
iSMA-B-MINI/MIX BACnet User Manual Module Input Results DO Switch Priority Array Present Value Digital Output Status Flag Property Auto position NULL Default Default 0000 BINARY VALUE BINARY VALUE BINARY VALUE Manual position NULL TRUE 0010 BINARY VALUE Manual position NULL FALSE 0010 BINARY VALUE...
Page 53
iSMA-B-MINI/MIX BACnet User Manual Property Required Proprietary Writable Property ID Data Type Description Name OBJECT_IDENTIFI From BO:0 to BO:3 OBJECT_NAME TO-x OBJECT_TYPE PRESENT_VALUE PRESENT_VALUE property STATUS_FLAGS STATUS FLAG property EVENT_STATE OUT_OF_SERVIC OUT OF SERVICE property POLARITY PRIORITY_ARRAY RELINQUISH_DE FAULT Table 26. Properties of the Triac Output object PRESENT_VALUE Property The Present Value property stores information about the actual state of the triac output.
iSMA-B-MINI/MIX BACnet User Manual STATUS FLAG Property The Status Flag property contains information about the status of object status. This property consists of 4 binary flags. Each flag is described in the table below. Module Input Results TO Switch Priority Array Present Value Digital Output Status Flag Property...
Page 55
iSMA-B-MINI/MIX BACnet User Manual Property Require Proprietar Writable Property Data Type Description Name RELINQUISH_D EFAULT This property stores INCREMENT percentage value of PWM output duty cycle. Output operation mode is defined by TO_CONFIGURATION object. COV INCREMENT Property OUTPUT_TYPE 4001 Enumerate HAND_STATUS 3014 Boolean...
iSMA-B-MINI/MIX BACnet User Manual Module Input Results TO Switch Priority Array Present Value Digital Output Status Flag Property Auto position NULL Default Default 0000 DUTY VALUE DUTY VALUE ON/OFF Manual position NULL 100% 0010 DUTY VALUE Manual position NULL 0010 DUTY VALUE Table 29.
iSMA-B-MINI/MIX BACnet User Manual This configuration is also available in the PWM VALUE object as the OUTPUT_TYPE Property 4001. 8.6 Special Application Modes 8.6.1 Special Application Modes for 4I4O-H, 4I4O-H-IP, 4U4O-H, and 4U4O-H-IP The 4I4O-H, 4I4O-H-IP, 4U4O-H, 4U4O-H-IP modules have simple built-in applications, which can be used to control building devices.
Page 58
iSMA-B-MINI/MIX BACnet User Manual Value OPERATING MODE Heating (4U4O-H and 4U4O-H-IP only) Cooling (4U4O-H and 4U4O-H-IP only) Table 33. The Input Mode object value list The operating mode can be changed by entering the right value into the Input Mode object.
Page 59
iSMA-B-MINI/MIX BACnet User Manual the relevant COMMAND object. The outputs can be also overwritten by the DIGITAL OUTPUT object, which allows remote control from the BMS. Time Relay NO [s] In this mode, if the output value is false, the rising edge on the digital input sets the output to true.
Page 60
iSMA-B-MINI/MIX BACnet User Manual Figure 40. The heating mode algorithm WARNING! In case if the temperature sensor fails (if it is disconnected or shorted), the heating mode does not work, and the output remains in the false state. Cooling Mode (4U4O-H and 4U4O-H-IP Only) In this mode, the output is controlled like a typical thermostat, based on the Setpoint object and Control value (Input signal) with a differential parameter defined in the Differential object.
iSMA-B-MINI/MIX BACnet User Manual Figure 41. The cooling mode algorithm WARNING! In case if the temperature sensor fails (if it is disconnected or shorted), the heating mode does not work, and the output remains in the false state. 8.6.3 MODE TIME Object (Analog Value: 26-29) This object contains the time value for TIME RELAY modes.
iSMA-B-MINI/MIX BACnet User Manual 8.6.7 DIFFERENTIAL Object (Analog Value: 34-37) The DIFFERENTIAL objects contain values, which are used in heating/cooling modes (4U4O-H and 4U4O-H-IP only) as the differential for heating/cooling control algorithm. The Setpoint objects and Differential objects create a deadband of the Control values, which has no influence on the output.
iSMA-B-MINI/MIX BACnet User Manual 9 Web Configuration This section outlines all information specific to configuring IP modules in a web server. WARNING! Please note that web configuration features are available only for IP versions for the MINI/MIX modules. 9.1 Web Server Access All IP version modules are equipped with a built-in web server, which allows for showing the status of the module and for changing the configuration.
iSMA-B-MINI/MIX BACnet User Manual 9.3 Local I/O Status and Configuration 9.3.1 Universal Inputs This page allows for entering the configuration parameters and showing the actual value of the universal inputs. To open this page, please navigate to the Local I/O tab and choose Universal Inputs from the submenu.
Page 65
iSMA-B-MINI/MIX BACnet User Manual WARNING! To save changes, please use the “Submit” button. Configuration of Special Application Modes This page allows for entering the configuration parameters and showing the actual value of Special application modes. To open this page, please navigate to the Local I/O tab and choose Universal Inputs from the submenu.
iSMA-B-MINI/MIX BACnet User Manual WARNING! To save changes, please use the “Submit” button. 9.3.2 Digital Inputs This page allows for entering the configuration parameters and showing the actual value of the digital inputs. To open this page, please navigate to the Local I/O tab and choose Digital Inputs from the submenu.
iSMA-B-MINI/MIX BACnet User Manual Figure 48. The MIX38-IP Digital Outputs page The Digital Output table contains the following fields: • State (read/write): the actual state of the digital output; • Default State (read/write): the output state after power-up and watchdog operation; •...
iSMA-B-MINI/MIX BACnet User Manual • Hand State Output (read-only, MINI series only): manually overrides the status of the potentiometer; • BACnet COV Increment (read/write): change of the state sending threshold value. WARNING! To save changes, please use the “Submit” button. 9.4 RS485 Configuration This page allows to enter the configuration parameters and show the information of the controller’s RS485 port.
Page 69
iSMA-B-MINI/MIX BACnet User Manual Figure 51. The IP configuration page This page allows for setting parameters such as: • IP Address (read/write): the IP address of the controller’s Ethernet interface; • Mask (read/write): the network mask; • Gateway (read/write): the network default gateway; •...
Page 70
iSMA-B-MINI/MIX BACnet User Manual WARNING! To save changes, please first click the “Submit” button, and then the “Reboot” button. What is BBMD? The BACnet/IP Broadcast Management Device (BBMD) is a device added to the BACnet network, which broadcasts messages discovering devices on the network. The BBMD solution allows to overcome an issue of standard IP routers, which cannot forward BACnet messages for BACnet networks on multiple IP subnets (two or more).
iSMA-B-MINI/MIX BACnet User Manual To register the iSMA Module as a foreign device, sending a request is necessary. The BBMD server IP address and UDP port must be filled accordingly to the server configuration. Using the “Send Request” button in the BACnet Register us as Foreign Device field, a device is being registered to the BBMD server.
iSMA-B-MINI/MIX BACnet User Manual Figure 52. The Device Management page The procedure of changing the device password: • enter current device password in the Current Device Password field; • enter the new device password in the New Device Password field; •...
iSMA-B-MINI/MIX BACnet User Manual 10 List of BACnet Objects BACnet Name BACnet Type Access Description UI-1 Analog Input Read-only Universal input current value UI-2 Analog Input Read-only UI-3 Analog Input Read-only UI-4 Analog Input Read-only UI-5 Analog Input Read-only UI-6 Analog Input Read-only UI-7...
Page 74
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description BI-12 Binary Input Read-only BO-1 Binary Output Read/write Digital output current value BO-2 Binary Output Read/write BO-3 Binary Output Read/write BO-4 Binary Output Read/write BO-5 Binary Output Read/write BO-6 Binary Output Read/write BO-7 Binary Output...
Page 75
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description BI-2_COUNTER Analog Value Read/write BI-3_COUNTER Analog Value Read/write BI-4_COUNTER Analog Value Read/write BI-5_COUNTER Analog Value Read/write BI-6_COUNTER Analog Value Read/write BI-7_COUNTER Analog Value Read/write BI-8_COUNTER Analog Value Read/write BI-9_COUNTER Analog Value Read/write BI-10_COUNTER Analog Value...
Page 76
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description UI-3_CONFIGURATIO Multistate Value Read/write UI-4_CONFIGURATIO Multistate Value Read/write UI-5_CONFIGURATIO Multistate Value Read/write UI-6_CONFIGURATIO Multistate Value Read/write UI-7_CONFIGURATIO Multistate Value Read/write UI-8_CONFIGURATIO Multistate Value Read/write UI-1_RESOLUTION Multistate Value Read/write Universal input resolution: - 12-bit (default) - 16-bit UI-2_RESOLUTION...
Page 77
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description AO-1_HAND_STATUS Multistate Value Read-only Analog output value in hand mode status: hand/auto AO-2_HAND_STATUS Multistate Value Read-only AO-3_HAND_STATUS Multistate Value Read-only AO-4_HAND_STATUS Multistate Value Read-only BO-1_HAND_STATUS Multistate Value Read-only Digital output value in hand mode status: hand/auto BO-2_HAND_STATUS Multistate Value...
Page 78
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description TO-2_PWM VALUE Analog Output Read/write TO-3_PWM VALUE Analog Output Read/write TO-4_PWM VALUE Analog Output Read/write TO-1_CONFIGURATIO Multistate Value Read/write Triac output operation mode configuration, options: - digital output - PWM TO-1_CONFIGURATIO Multistate Value Read/write...
Page 79
iSMA-B-MINI/MIX BACnet User Manual BACnet Name BACnet Type Access Description BI-2_BLOCK_INPUT Binary Value Read/write BI-3_BLOCK_INPUT Binary Value Read/write BI-4_BLOCK_INPUT Binary Value Read/write BI-1_COMMAND Binary Value Read/write Digital input remote command BI-2_COMMAND Binary Value Read/write BI-3_COMMAND Binary Value Read/write BI-4_COMMAND Binary Value Read/write For MINI 4U4O-H and 4U4O-H-IP only BI-1_SETPOINT...
Page 80
iSMA-B-MINI/MIX BACnet User Manual 11 List of Supported Temperature Sensors • 10K3A1 • 10K4A1 • 10K Carel • 20K6A1 • 2.2K3A1 • 3K3A1 • 30K6A1 • SIE1 • TAC1 • SAT1 • PT1000 • NI1000 • NI1000 21C (ºC) • NI1000 LG (ºC) •...