1) WARNING:
 USE COVER BOLTS CLASS A4-70
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 POTENTIAL ELECTROSTATIC HAZARD
 FOR INDOOR OR OUTDOOR USE
 TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED WITHIN 18 INCHES OF
CONDUIT
CAUTION - RISK OF ELECTRIC SHOCK -
MORE THAN ONE DISCONNECT MAY BE
REQUIREDTO DE-ENERGIZE THE
EQUIPMENT BEFORE SERVICING
AVERTISSEMENT:
UTILISER COUVRIR BOULONS CLASSE A4-
70
NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - VOIR LES
INSTRUCTIONS
POUR USAGE INTÉRIEUR OU EXTERIEUR
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LES CONDUITES DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
POUCES DE L'ENFERMEMENT
ATTENTION - RISQUE DE CHOC
ELECTRIQUE - PLUSIEURS SECTIONNEURS
PEUVENT ETRE NECESSAIRES POUR
COUPER L'ALIMENTATION DE
L'APPAREILLAGE AVANT
D'ENTREPRENDRE L'ENTRETIEN
2) Rating & Marking Information
2.1 NEC & CEC Class / Division Ratings for US / Canada
The GNExCP7 callpoints comply with the following
standards:
UL 60947-4-1 Low voltage switchgear and controlgear – Part 4-1:
Contactors and motorstarters – Electromechanical contactors and
motorstarters – Ed. 3 Rev. date 2017/10/
CSA C22.2 NO. 60947-4-1-14 Low voltage switchgear and
controlgear – Part 4-1: Contactors and motorstarters –
Electromechanical contactors and motorstarters – Ed. 2 - Issue Date
2014/01/04
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D202-00-211-IS
GNExCP7-PB-S, GNExCP7-PB-D, GNExCP7-PM-S, GNExCP7-PM-D,
GNExCP7-PT-S & GNExCP7-PT-D CALL POINTS
Issue 4
16-12-2022
INSTRUCTION MANUAL
For use in Flammable Gas Atmospheres
The GNExCP7 callpoints are rated as follows:
Class I Div 2 Group ABCD T6 Ta -55°C to +60°C
Class II Div 2 Group FG T4 Ta -55°C to +60°C
Class III Div 1 & 2 Ta -55°C to +60°C
2.2 NEC Class / Zone ratings US
The GNExCP7 callpoints comply with the following
standards:
UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment
- General requirements
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment
protection by flameproof enclosures "d"
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31:
Equipment dust ignition protection by enclosure "t"
The GNExCP7 callpoints are rated as follows:
Class I Zone 1 AEx db IIC T6 Gb (Ta -55°C to +60°C)
Zone 21 AEx tb IIIC T125°C Db (Ta -55°C to +60°C)
2.3 CEC Class / Zone ratings Canada
The GNExCP7 callpoints comply with the following
standards:
CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part
0: Equipment – General requirements
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part
1: Equipment protection by flameproof enclosures "d"
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres –
Part 31: Equipment dust ignition protection by enclosure "t"
The GNExCP7 callpoints are rated as follows:
Class I Zone 1 Ex db IIC T6 Gb X (Ta -55°C to +60°C)
Zone 21 Ex tb IIIC T125°C Db (Ta -55°C to +60°C)
2.4 ATEX / IECEx / UKEX Certification
The GNExCP7 callpoints comply with the following
standards:
EN60079-0:2018 / IEC60079-0:2017 (Ed 7): Explosive Atmospheres
– Part 0: Equipment. General requirements
EN60079-1:2014 / IEC60079-1:2014 (Ed 7): Explosive Atmospheres
- Part 1: Equipment protection by flameproof enclosures "d"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): Explosive
Atmospheres - Part 31: Equipment dust ignition protection by
enclosure "t"
sales@e2s.com
Sheet 1 of 7
Tel: +44 (0)208 743 8880
www.e2s.com
Fax: +44 (0)208 740 4200

Advertisement

Table of Contents
loading

Summary of Contents for E2S GNExCP7-PB-S

  • Page 1 INSTRUCTION MANUAL GNExCP7-PB-S, GNExCP7-PB-D, GNExCP7-PM-S, GNExCP7-PM-D, GNExCP7-PT-S & GNExCP7-PT-D CALL POINTS For use in Flammable Gas Atmospheres 1) WARNING: The GNExCP7 callpoints are rated as follows:  USE COVER BOLTS CLASS A4-70  DO NOT OPEN WHEN AN EXPLOSIVE Class I Div 2 Group ABCD T6 Ta -55°C to +60°C ATMOSPHERE IS PRESENT Class II Div 2 Group FG T4 Ta -55°C to +60°C...
  • Page 2: Installation Requirements

    All units have a rating label, which carries the following Dust Groupings: important information: - Group IIIA Combustible Flyings Model No.: GNExCP7-PB-S (Single Switch) Group IIIB Non-conductive Dust GNExCP7-PB-D (Dual Switch) Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications:...
  • Page 3: Location And Mounting

    M6 cover screws are Class A4-70 stainless steel and only screws of this category can be used for the enclosure. _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D202-00-211-IS Issue 5 16-12-2022...
  • Page 4: Cable Connections

    For Single Switch models GNExCP7-PT-S / GNExCP7-PM-S used and also meet the requirements of the current Ex ‘d’ / GNExCP7-PB-S: flameproof installation standards EN 60079-14 / IEC60079- Max. ambient temperature (°C) req.
  • Page 5 _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D202-00-211-IS Issue 5 16-12-2022...
  • Page 6 If lower value resistors than seen on table are required it may All models can be fitted with series resistors, end-of-line be possible to configure but seek advice from E2S to ensure monitoring resistors, monitoring diodes and zener diodes if compliance is still maintained.
  • Page 7 PFD (hazardous failure) 2.3 x 10 Proof Test Interval Up to 1 year _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D202-00-211-IS Issue 5 16-12-2022 Sheet 7 of 7...
  • Page 8 (Resistor polarity is unimportant) Terminals (4/5) & (6) closed Terminals (4/5) & (6) closed POSITIVE (+) COMMON POSITIVE (+) COMMON (IF DIODES SUPPLIED & CONFIGURED BY E2S) (IF DIODES SUPPLIED & CONFIGURED BY E2S) M/S 1 M/S 1 M/S 1...
  • Page 9 (Resistor polarity is unimportant) COM EOL COM EOL POSITIVE (+) COMMON POSITIVE (+) COMMON (IF DIODES SUPPLIED & CONFIGURED BY E2S) (IF DIODES SUPPLIED & CONFIGURED BY E2S) DIODE DIODE 4A - Circuit as shown in Unoperated condition 4A - Circuit as shown in Unoperated condition 4A - Circuit as shown in Unoperated condition Terminals (1) &...
  • Page 10 Terminals (1) & (4) M/S 1 and M/S 2 open Terminals (1) & (4) M/S 1 and M/S 2 open Contact E2S sales for special wiring requests Terminals (1) & (3) M/S 1 and (5) & (7) M/S 2 closed Terminals (1) &...
  • Page 11 See Sht 1 GNExCP7 [ ] [S] [P] SWITCH TYPE: [S] - Single Microswitch TERMINAL TYPE [P] - PCB ACN0102 RNP 15-04-2022 GNExCP7 [ ] [D] [P] SWITCH TYPE: [D] - Double Microswitch TERMINAL TYPE [P] - PCB EOL RESISTOR FIT IN 2 &...
  • Page 12: Eu Declaration Of Conformity

        Manufacturer:      European Safety Systems Ltd.        Impress House, Mansell Road, Acton        London, W3 7QH        United Kingdom    Authorised Representative:  E2S Warnsignaltechnik UG        Charlottenstrasse 45‐51        72764 Reutlingen        Germany    Equipment Type: GNExCP7‐BG, GNExCP7‐PB, GNExCP7‐PM, GNExCP7‐PT    Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX)  Notified Body for EU type Examination (Module B):  UL International Demko A/S  Notified Body No.: 0539 ...
  • Page 13 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC-099_Issue_A Quality Assurance Manager Date and Place of Issue: London, 24/02/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-099_Issue_A - Page 1 of 1 - QAF_252_Issue_5...

Table of Contents