E2S A141 Instruction Manual

E2S A141 Instruction Manual

High level audible warning system / battery backup

Advertisement

Quick Links

1)
Introduction
The A141 high level audible warning system is an
effective wide area warning alarm system and
can be used where there is a requirement to
attract attention over large areas and also where
potential high levels of background noise exist.
The system comprises of a central control unit
which is configured to drive an audible horns
containing four driver units.
The control unit produces forty five different alarm
sounds (tones) that are selectable using an
internal dipswitch (see tone table page 3 for
available tones) including a stage 2 and stage 3
alarm option.
Each audible horn is capable of producing a
range of loud warning signals with output levels
at
one
meter
of
approximately
depending on tone selected.
Both the control unit and horns are suitable to
mount either indoors or outdoors in a number of
mounting configurations with ingress protection to
IP65.
This particular unit is also fitted with a Battery
backup system with fault monitoring with relay
terminals and a set of remote start and stop
terminals.
2)
Operating and Marking
All
units
have
the
requirements and limitations.
Audible Horn Units
Unit Type No.:
A141
Operating Temp: -20 to +55C
IP Rating:
IP65
Horn weight:
14kg
European Safety Systems Ltd.
Document No. D161-00-201-IS_Issue_E 12-02-13
INSTRUCTION MANUAL
A141 High Level Audible Warning System / Battery backup
141dB(A)
following
operating
Impress House, Mansell Road, Acton, London W3 7QH
Sheet 1 of 5
Control Panel
Unit Type No.
A141AC230GB
Input Voltage:
115 or 230VAC (90V to 264V AC range)
Operating Temp: -20 to +55C
IP Rating:
IP65
Marking:
Control Unit weight : 23kg
3)
Installation Requirements
Always de-energize control unit before removing
cover.
The installation of the units must be in
accordance with any local codes that may apply
and should only be carried out by a competent
electrical engineer who has the necessary
training.
3)
Power Supply Selection
It is important that a suitable power supply is run
the control unit. The power supply selected must
have the necessary capacity to provide the input
current to the control unit.
The following table shows the input current taken
by the various control unit configurations units:-
AC Unit Type
Input
No. Horns
Voltage Current I/P Volts
A141AC230GB
115V AC 4.2A
230V AC 1.95A
Table 1: Variants and power requirements
Current levels shown above are for the nominal
input voltage. The input current will vary
according to the voltage input level and the tone
selected.
The above table also shows the maximum and
minimum voltages at which the control units can
be operated.
4)
Cable Selection
When selecting the cable size consideration must
be given to the input current that the control unit
draws (see table above) and the length of the
cable run.
sales@e2s.com
www.e2s.com
Input
Range.
90-264V AC
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S A141

  • Page 1 INSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup Control Panel Unit Type No. A141AC230GB Input Voltage: 115 or 230VAC (90V to 264V AC range) Operating Temp: -20 to +55C IP Rating: IP65 Marking: Control Unit weight : 23kg...
  • Page 2: Battery Installation

    INSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup Earthing AC powered control units must be connected to a good quality earth. The unit is provided with internal earthing terminal which is located next to the power terminal (See figure 2).
  • Page 3: Start Stop Switches

    INSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup stop switch is momentarily opened to stop the There is a set of contacts that change over on a unit. system fault, this includes a battery fault or a charging fault.
  • Page 4 INSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup 12) Remote Sounder Operation AC Units Second and Third Stage Tone Selection AC Units First Stage Tone Selection To select the second and third stage tones on the A141 audible alarm system, connect to the S2...
  • Page 5 INSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup Fig 3: Schematic Circuit Diagram of AC unit with stages S2 and S3 with negative switching European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com...

This manual is also suitable for:

A141ac230gb