Warnings
USE COVER BOLTS CLASS A4-70
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
POTENTIAL ELECTROSTATIC HAZARD
ALL ENTRIES M20 X 1.5
DO NOT OPEN WHEN ENERGIZED
IF TEMPERATURE EXCEEDS 70°C AT
ENTRY OR 80°C AT BRANCHING POINT
USE SUITABLE RATED CABLE AND CABLE
GLANDS
1) Rating & Marking Information
2.1 ATEX / IECEx / UKEX Certification
All units have a rating label, which carries the following
important information:
STExCP8-BG-S (Single Switch)
Model No.:
STExCP8-BG-D (Dual Switch)
Input Voltage:
DC Units
AC Units
series or end-of-line devices only)
STExCP8-BG-S Codes:
Ex db IIC T6 Gb Ta. -55°C to +70°C
STExCP8-BG-D Codes:
Ex db IIC T5 Gb Ta. -55°C to +70°C
Ex db IIC T6 Gb Ta. -55°C to +60°C
DEMKO 15 ATEX 1589X
Certificate No.
IECEx ULD 15.0018X
UL21UKEX2133X
ATEX Marking
Equipment Group and
Category:
CE Marking
Notified Body No.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D204-00-001-IS
STExCP8-BG-S & STExCP8-BG-D CALL POINT
For use in Flammable Gas Atmospheres and Marine Environments
48Vdc Max
250Vac max (units without
II 2G
2813
Issue 7
16-12-2022
INSTRUCTION MANUAL
(ATEX / IECEx / UKEX / DNV GL)
STExCP8-BG
UKCA Marking
Notified Body No.
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Zone 1
Zone 2
Gas Groupings:
Group IIA
Group IIB
Group IIC
Temperature Classification:
T1
T2
T3
T4
T5
T6
IP Rating:
Equipment Category:
Equipment Protection Level:
Ambient Temperature Range:
2.2 DNV GL Type Approval
The units have been tested and approved for the installation
on ships in the following locations:
Temperature:
Humidity:
Vibration:
Sheet 1 of 6
0518
Explosive gas air mixture likely to occur in
normal operation.
Explosive gas atmosphere not likely to
occur in normal operation but may be
present for short periods.
Propane
Ethylene
Hydrogen and Acetylene
450ºC
300ºC
200ºC
135ºC
100ºC
85ºC (For Dual Switch models only up to
Tamb 60°C)
IP66/67 to EN/IEC60529 and IP6X to
EN/IEC60079-0, EN/IEC60079-31
2G
Gb
-55°C to +70°C Gas Groups IIA, IIB and IIC
Class A,B,C & D (all locations including
open decks and masts)
Class A & B (all locations)
Class A (all locations except installation on
machinery such as combustion engines,
compressors, pumps, including piping on
such machinery)
www.e2s.com