Procedure for device configuration with GSD file
Table 2- 3
Steps for configuring following a Y-link/redundant H station
Step
Action
1
Select the SIMATIC 400 station in the component view.
Select the "Edit > Open Object" menu command.
The HW Config opens.
2
If the hardware catalog is not visible, select the "View > Catalog" menu command.
Install the necessary GSD file for the motor starter:
Menu command "Options > Install GSD file".
In the standard hardware catalog, open the "PROFIBUS DP > Additional Field Devices > I/O > ET 200S > ET
200S HighFeature" folder.
Open the folders "Additional Field Devices > I/O > ET 200S > ET 200S High Feature" one after the other
Use a drag-and-drop operation to move the ET 200S station and all required modules, such as power
modules and motor starters, to the "DP master system". The "Properties" dialog box opens.
Enter the PROFIBUS address.
This is the same address as the address of the device station of the motor starter.
Click "OK".
The settings are accepted.
3
Compile the hardware configuration: "Station > Save and Compile".
Set the PG/PC interface to CP 5613 A2 (PROFIBUS)
Download the automation station configuration: "PLC Download".
SIRIUS Motor Starter PCS 7 Library "V7.1+SP2"/ "V8 Migration V8.0+SP1"
Getting Started, 08/2013, A5E02897539020A/RS-AA/005
First steps for the project
2.2 Configuring the device hardware
17