1) Product Table
D2xB1LD3DC024
*max. rms current at worst-case voltage in voltage range.
For detailed current ratings of the device please see Section 13.
Table 1: Electrical Ratings.
2) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
Avertissement:
NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
3) Rating & Marking Information
3.1 Public Mode Fire Alarm Ratings
The D2xB1LD3DC024 is certified for use as a public mode
visual alarm device in accordance with UL1971 Third Edition
and UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition.
All models are approved for use as a Visual Appliance for use
in Private Mode Fire Alarm Systems in accordance with
UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition.
See fire instruction manual D211-00-471-IS-SC-UL
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D211-00-471-IS
Model
Issue 3
D2XB1LD3
Nom. Voltage
24Vdc
Regulated (16-33Vdc)
3.3. ATEX / IECEx / UKEx Ratings
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres - Equipment Dust Ignition Protection by
Enclosure "t"
D2xB1LD2:
Certificate No.
ATEX Mark, Equipment
Group and Category:
CE Marking
UKCA Marking
20-08-22
Voltage Range
Standards
Ratings
Ex ec IIC T4 Gc Ta -40°C to +50°C
Ex tc IIIC T75°C Dc Ta -40°C to +50°C
DEMKO 14 ATEX 4786493904X
IECEx ULD 14.0004X
UL21UKEX2131X
www.e2s.com
Max Operating
Current*
528mA
II 3G
II 3D
Tel: +44 (0)208 743 8880