Installation Space Requirements

• Position the unit on a horizontal surface. Any tilt in the unit should be 3° or less to the horizontal.
• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation space requirements
below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.
• Secure as much installation space around the unit as the location allows, as more space will result in more efficient operation.
Wall facing one side
More than
More than
3-15/16 (100)
13-3/4 (350)
47-1/4
(1200)
or less
Side view
Walls facing three sides
More than
1-15/16 (50)
Top view
Selecting a Location for Installation of
the Indoor Units
• The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and
indoor units, are listed below.
• Refrigerant piping must be kept to a minimum.
The suggested shortest pipe length per room is 10ft (3m), in order to avoid noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used.)
Outdoor unit capacity class
Piping to each indoor unit
Total length of piping between all units
Level
difference:
Level
49-1/4ft (15m)
difference:
max.
24-5/8ft (7.5m)
max.
If the outdoor unit is positioned higher than the indoor units.
5
Walls facing two sides
More than 3-15/16 (100)
More than 13-3/4 (350)
unit: inch (mm)
2MXS∗, 2MXL∗
164ft (50m) max.
Indoor unit
Outdoor unit
More
than
3-15/16
(100)
More than
1-15/16 (50)
When installed as in the figure on the left, it is recommended to either
change the orientation of the outdoor unit outlet side or use the air direction
adjustment grille (sold separately).
3MXS∗, 4MXS∗, 3MXL∗
82ft (25m) max. 10ft (3m) min.
230ft (70m) max.
Level
difference:
49-1/4ft (15m)
max.
If the outdoor unit is positioned lower than
one or more indoor units.
More than
More than
3-15/16 (100)
13-3/4
(350)
More than
13-3/4 (350)
Top view
Level
difference:
24-5/8ft (7.5m)
max.
Indoor unit
More than
1-15/16 (50)
Outdoor unit
English