13. INSTALLING DUCT WORK
Install all duct work to meet current
standards:
• ASHRAE/NFPA 90, Standard for Installation of
Warm air Heating and air Systems.
• State, provincial, and local codes
Failure to follow these standards could reduce air flow
or increase air leakage, resulting in reduced system
performance or unit damage.
TABLE 1 - CFM aND MOTOR SPEED SELECTION
INDOOR BLOWER CFM - VPC & VPP MODELS
Motor
Model #
Speed
HIgH
vPC/vPP**09
MED
LOW
HIgH
vPC/vPP**12
MED
LOW
HIgH
vPC/vPP**18
MED
LOW
HIgH
vPC/vPP**24
MED
LOW
INDOOR BLOWER CFM - VPH MODELS
Motor
Model #
Speed
HIgH
vPH0209
MED
2 ROW H/W COIL
LOW
HIgH
vPH0212
MED
2 ROW H/W COIL
LOW
HIgH
vPH0218
MED
2 ROW H/W COIL
LOW
HIgH
vPH0318
MED
3 ROW H/W COIL
LOW
HIgH
vPH0224
MED
2 ROW H/W COIL
LOW
HIgH
vPH0324
MED
3 ROW H/W COIL
LOW
NOTE: aLL uNITS SHIPPED FaCTORy CONNECTED aT MEDIuM SPEED
12
0.05
0.10
0.15
445
435
425
350
340
330
280
275
270
470
460
450
370
360
350
295
290
285
775
760
745
640
630
620
450
445
440
1070
1045
1020
930
920
910
820
815
810
0.05
0.10
0.15
435
425
415
340
330
320
275
270
265
460
450
440
360
350
340
290
285
280
735
715
695
620
605
590
445
440
435
700
680
660
610
595
580
440
435
430
950
930
910
890
860
840
805
800
790
910
890
870
840
815
790
790
775
760
For all units, design duct systems within the maximum
external static pressure limits indicated in Table 1.
SUPPLY AIR DUCT WORK
Duct attaching hardware must only be used on the
supply air outlet flanges. Optional electrical heater is
located under the top panel near these flanges. Do not
drill or use screws in this area.
Supply air duct (plenum) connection
must be at least the same size as the
unit supply air opening. Seal supply air
duct work to unit casing, walls, ceilings
or floors.
ExTERNaL STaTIC PRESSuRE
0.20
0.25
415
400
320
310
265
255
440
425
340
330
280
270
725
705
610
600
435
430
995
970
900
890
805
800
ExTERNaL STaTIC PRESSuRE
0.20
0.25
400
385
310
300
255
245
425
410
330
315
270
260
675
650
575
560
430
425
640
615
565
550
420
410
885
860
810
780
775
760
850
820
765
740
740
720
FORM 145.20-IOM1 (908)
0.30
0.35
0.40
385
370
355
300
285
270
245
235
220
410
395
375
315
300
285
260
245
230
685
660
635
585
570
555
420
405
390
945
915
885
875
860
840
790
780
765
0.30
0.35
0.40
370
355
335
285
270
255
235
220
205
395
375
355
300
285
270
245
230
215
625
595
565
545
525
505
415
410
395
590
560
530
530
510
495
400
390
380
835
810
780
750
720
690
740
715
685
795
770
740
715
690
660
690
660
630