Controller Parameters; Unit Equipment; Selecting The Type Of Heating And Cooling - Ventair CU24V1 Operation Instruction Manual

Controller for air handling units
Table of Contents

Advertisement

4 C
ONTROLLER PARAMETERS
4.1 U
NIT EQUIPMENT
Setting a program to the CU24V1 controller is done remotely using the RMC20 panel. Before setting a
program, the unit should be switch off (In the display the message "UNIT IS OFF" should be displayed).
You can choose from a ready-made application or user application that allows you to manually
configure the application by editing individual options.
Name
Default value
AP
USER
4.1.1
S
ELECTING THE TYPE OF HEATING AND COOLING
Beware:
The bellow settings are valid when the heat pump mode at page #11 of the menu is off, it means the
following setting is done: Heat pump: No
Heating:
water: Water coil heater with control signal at Y3 output
electr:
Electric heater with control signal at PWM output P2
none:
No heater
Outputs Y3 and P2 of the CU24V1 controller work independently of the type of heater, while the E1
input, depending on the type of heater, functions as an anti-freeze alarm or a high temperature alarm..
Heating
Y3
0-10V:
water
heating
control
0-10V:
electr
heating
control
Cooler:
Water: Water coil cooling with smooth control in PI integration mode.
agregat-1:
Single stage cooling unit with ON/OFF control
agregat-2:
Two-stage cooling unit with control outputs at Q3 and Q4 in PI integration
mode
None:
No cooler
The Y4 output of the CU24V1 is active regardless of the type of cooling (water, chiller-1, or chiller-2)
and can be used to control the valve or chiller. On the other hand, the output Q3 is used to control the
pump or the first stage of the chiller depending on the selection, and Q4 confirms the cooling mode or
controls the second stage of the chiller.
Options
USER
W-001 ÷ E-012
CU24V1 outputs
P2
PWM output
230 VAC: Pump start.
for electric
heater
PWM output
230 VAC: Enable working for
for electric
electric heaters.
heater
Descriptions
User application:
Manual adjustments by users
Application for supply-extraction units
U1-U2
Frost alarm of water
heating coil
Hi temperature alarm
of electric heater
9
CU24V1 input