Cooling Parameters - Ventair CU24V1 Operation Instruction Manual

Controller for air handling units
Table of Contents

Advertisement

Heating enabled
4.2.3
C
OOLING PARAMETERS
Name
Default value
PBAND
30.0°C
INT
100 sec
HYS
1.5°C
o
CDIS
15
C
CDIS parameter operation scheme
Cooling disabled
Hysteresis
HDIS-1
Enable heating
Disable heating
Range
0 ÷ 999.9°C
0 ÷ 6000 sec
0.5 ÷ 10.0°C
o
10 ± 22
C
Hysteresis
CDIS
Disable cooling
HDIS
Outdoor temperature
Description
Proportional band.
Setting PBAND = 0 means ON / OFF
operation with hysteresis and the entered
HYS parameter.
Integral time
Hysteresis for two-position control.
If the PBAND = 0, hysteresis determines
the HYS parameter
Operation ON/OFF
Outside temperature below which the
cooling is turned off (the WINTER mode).
CDIS+1
Enable cooling
Outdoor temperature
12