Basic Parameters; Standard Controller Inputs And Outputs - Ventair CU24V1 Operation Instruction Manual

Controller for air handling units
Table of Contents

Advertisement

2.3 B
ASIC PARAMETERS
Type
Resistive
Inputs
Analog
Digital
Analog
Outputs
Modulated
Relay
RS485 serial port: 2 ports
Communication
Distance: up to 50m
Communication protocol MODBUS
2.4 S
TANDARD CONTROLLER INPUTS AND OUTPUTS
G0, G
Power supply: 24 VAC ± 10%, 50/60 Hz, input: 6VA (outputs P1, P2 unloaded)
M
System ground voltage
B1-B4
Resistance inputs PT1000
E1-E5
Potential-free resistance inputs
X1
Analog input 0-10V
Q1 - Q4
Relay output – normally open
DA
Relay output – 24 V
U1-U2
Relay output – 230 V
Y1-Y6
Voltage outputs 0-10 V DC
P1, P2
24 V DC modulated outputs; for continuous regulation of electric heaters. Controlled
devices should be connected between P1 (+) and ground M (-), or P2 (+) and ground M (-)
A1, B1
Serial interface RS485 Nr. 1
A2, B2
Serial interface RS485 Nr. 2
Digital outputs
Water heater frost protection thermostat
E1
Electric heater alarm
E2
Inlet and outlet filter pressure switch
Confirmation of supply fan operation, confirmation of
E3
exhaust fan operation, confirmation of rotary
recuperator operation, supply fan pressure switch
E4
Cooling source alarm
E5
Enable operation / Service switch
PP
EPS signal
Nr
Characteristic
4
PT1000 type, range -25 ... +70 °C
1
0-10V
5
Free potential contact
6
0-10V / 2mA
2
21V ±2VDC / 50mA
5
250VAC, 3A / Resistive load
When the
In an alarm
system works
condition
properly
closed
Freeze alarm
closed
Hi temperature
open
closed
Engine alarm
Cooling source
open
alarm
open
Disable operation
closed
Disable operation
6