Ventair CU24V1 Operation Instruction Manual page 21

Controller for air handling units
Table of Contents

Advertisement

dot should be placed artificially Ex.: Reading
the value 257 should be treated as 25.7%
2. The value 0x8000 means, the parameter is
not available.
Alarms register bit alignment
Read and write
Alarms register are 32-bit wide
Desired values: read/write
Device operating state
Sensed values
1. The sensed values have 1/10 precision.
After reading the sensed value it should be
divided by 10.
Ex: Reading the number 257 should be
treated as 25.7
2. Reading the value 0xFFFF means that ,
the parameter does not exist
Start/Stop command and system
operating state
Parameters – group 1
Parameters – group 2
0 –............................................................................
1 – R1H: current alarm - High register .............................
2 – R1L: current alarm – Low register .............................
0 – Desired temperature for the main heating/cooling..........
2 – Desired value for CO2 control....................................
3 – Fan gear ....................................................
Writing- 5 values:
0 – Gear according to the controller setting
1 – gear 1
2 – gear2
3 – gear3
4 – gear4
Reading- 4values:
0 – gear 1
1 – gear 2
2 – gear 3
3 – gear 4
4 – Running mode ......................................................
Writing - 3 values:
0 – Running mode according to the controller setting
1 – AUTOMATIC
2 – MANUAL
Reading - 2 values:
0 – AUTOMATIC
1 – MANUAL
5 – Desired temperature for preliminary heater .............
7 – Fan running speed ..............................................
0 – Register 1
1 – Register 2
0 – Indoor/exhaust temperature......................................
1 –CO2 sensed value.....................................................
3 – Supply temperature................................................
6 – Outdoor temperature..............................................
8 – Exchanger exhaust air temperature...........................
25-Ground Heating Exchanger temperature.....................
Start/Stop command
Write: Start=0x00AA, Stop=0x0055
Read: System operating state
0 – system stopped by the operator
1 – system stopped by the ECO mode function
2 – system stopped by schedule
3 –
4 –
5 – System running
1 – MIN: Supply minimum temperature...........................
2 – MAX: Supply maximum temperature .........................
56 – HDIS: Heating disable outdoor temp. (Summer)..........
57 – CDIS: Cooling disable outdoor temp. (Winter).............
59 – FCOEF: Exhaust/Supply fan speed ratio ...................
19- Temperature control type .......................................
0 – Cascade control
1 – Supply control
.......
65280
65281
65282
65216
65218
65219
65220
65221
65223
21
65152
65153
64896
64897
64899
64902
64904
64921
64640
63233
63234
63288
63289
63291
63187