• A maximum of 64 registers can be written by Modbus function code 16 (see “Supported modbus functions codes”). • A maximum of 64 coils can be written by Modbus function code 15 (see “Supported modbus functions codes”). SIO-MB04THMS User Guide, 1st Edition...
Page 3
Stride Field I/O PRODUCT LABEL AND WIRING DIAGRAM Terminal block pinouts and wiring diagrams are printed on the side of the module, as shown below. SIO-MB04THMS User Guide, 1st Edition...
Page 4
Default: Tc K (05 Hex) TC S 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 TC T Description Input Type #1 TC B TC E TC N SIO-MB04THMS User Guide, 1st Edition...
Page 5
These registers contain the offset values for each input. The values are expressed in cents of mV for mV input and tenths of °C for Tc input. The register format is a 16 bit unsigned integer. SIO-MB04THMS User Guide, 1st Edition...
Page 6
The device interface includes five configuration categories, as shown by the navigation menu on the left of the screen on the next page. Hovering over a navigation button will display a tooltip to describe the selection. SIO-MB04THMS User Guide, 1st Edition...
Page 7
Click Save to apply and store the modified parameters. Wait for the device to reset. After modifying the network settings you will need to use the updated IP address to connect to the device, and may need to change the subnet mask on your PC. SIO-MB04THMS User Guide, 1st Edition...
(0 = power cycle has not occurred ; 1 = power cycle has occurred ). Click Save to apply and store the modified parameters. To read the parameters from the device click Refresh. SIO-MB04THMS User Guide, 1st Edition...
Page 9
• Firmware Version: shows the firmware version loaded on the device. • WebPage Version: shows the version of the web-based user interface loaded on the device. Do not disconnect power from the device during the upgrade process. SIO-MB04THMS User Guide, 1st Edition...
Page 10
Set the user name and password. • Username: set the user name to access the device. Default “admin”. • Password: set the password to access the device. Default “password”. Click Save to apply and store the modified parameters. SIO-MB04THMS User Guide, 1st Edition...
• Offset: sets an offset value to be added to the raw sensor reading to calibrate the sensor. • Set Same Input: sets all channels to the input type selected for the first channel (Analog In 0). Click Save to apply and save all changes on the page. SIO-MB04THMS User Guide, 1st Edition...
Page 12
To exit from the alarm condition, send any command to the device and reset the “Watchdog Event” coil. NOTE: When the device is switched off the state of the “Watchdog Enable” bit remains stored in EEPROM. SIO-MB04THMS User Guide, 1st Edition...