Lobley St SPS SP331 General (Electrical Manual (MPA) Multismart Manual Multitrode System Integrator Guide) General
5
Which tags should be integrated?
The tags available via Modbus or DN3 are listed in the profile documents, available from the MultiTrode
website – www.multitrode.com.
The points list is extensive.
Also, note that additional tags can easily be added to the points list. See the notes in sections 5.4 and
5.5).
Because of the pre-configured nature of the product there are a large number of tags available for
integration. There will often be many tags not used in a specific MultiSmart installation.
5.1 Examples of tags or points not used in an installation
The profile document includes DNP3 points (and Modbus points) for:
•
"Pump 1 Seal fault" – this fault will only exist when a pump seal sensor is wired into MultiSmart
and configured
•
"Well 1 Backup level invalid" – this fault only occurs when a backup level device is configured
•
"Well 2 Level" – this fault only occurs in 2 well applications
Therefore, there can be a large number of tags which will not be configured in any one installation.
5.2 Active Faults and Unacknowledged Faults
MultiSmart faults often have 3 states – active; unacknowledged and cleared
•
Active is the typical fault state where the fault condition is present
•
Unacknowledged is a very useful fault condition, indicating that the fault has occurred, the
source of the fault has cleared, but the indication remains for operations that the fault was
present
Therefore, 2 tags are often used for one fault, e.g. Under-voltage has 2 tags:
•
Faults.Station.UnderVoltage.Status.Active
•
Faults.Station.UnderVoltage.Status.Unacknowledged
The integration can include both tags, or simply the active tag.
Resetting the fault is now available when the fault is in the unacknowledged state. A number of fault
reset tags exist to allow pump and station faults to be cleared. Some of these can be seen in the
Intermediate 2-pump application (section 5.5).
5.3 Integration approach
We give 2 examples to make integration of a MultiSmart pump station as easy as possible. These are
indicative only, to assist integrators new to the product.
To see an example of a more extensive implementation, with a few hundred tags per site, review the
Outpost2 functional specification, available on www.multitrode.com
The definitive tag list is always the DNP3 and Modbus Slave profiles, available on the MultiTrode website.
Page 5 of 20
Q-Pulse Id VM357
MultiSmart Integrator Guide
Active 26/09/2013
MultiSmart_Integrator_Guide_R01.doc