Kubota GL6000-AUS Operator's Manual page 23

Diesel generator
Hide thumbs Also See for GL6000-AUS:
Table of Contents

Advertisement

A Connecting a motor.
When starting the motor, the voltage drops
immediately. The circuit may be opened if an
electromagnetic switch is connected to the same
circuit. When connecting two motors or more, make
sure the total current capacity of the motors does not
exceed the total rated current.
A Connecting to lights and electric heaters.
When connecting to lights or electric heaters, the
generator can be used up to the rated capacity.
When using a single phase, it can be used up to the
rated current.
A Power factor calculations.
The power factor calculation is used to determine
input of the electrical devices.
AC devices
Electric power (W)
= Voltage (V) × Current (A) ÷ Power factor
Power factors of commonly used devices are listed in
the following table.
Load type
Single-phase induction motors
Electric heaters, incandescent
lamps
Commutator motor
Fluorescent lamps, mercury
lamps
AC arc welder
A Ordinarily, a motor is rated in kW. This does not refer
to motor output.
Motor input (kVA)
Motor output (kW)
=
Motor efficiency × power factor
A If a lighting system is employed together with some
types of computers and inverter air-conditioners
and/or the regulated power supply for TV sets, the
lights might suffer flickering. This phenomenon does
not indicate a fault of the generator: it is caused by
poor matching between the above-mentioned
regulated power supply and the generator's
automatic voltage regulator. In such a case, modify
the load combination to eliminate the flickering.
PREPARATION TO SUPPLY THE ELECTRIC POWER
Power factor
0.4 to 0.75
1.0
0.8 to 0.95
0.4 to 0.9
0.4 to 0.6
11