Table 1.1 Ups Installation Environment - Mitsubishi Electric 2033G Series Owner Technical Manual

Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may
deteriorate insulation, shorten component life and cause
malfunctions.
Keep the installation environment per standard described as follows:
UPS Installation Environment
TABLE 1.1
No.
Item
1
Installation
location
2
Ambient
temperature
3
Relative
humidity
4
Altitude
5
Dust
6
Inflammable gas
following
IEC654-4
Part 4
2033G SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 3
Indoors
Minimum temperature: 32F(0C), Maximum temperature: 104F(40C) The
average temperature over any 24-hour period must be in the range 41 F (5C)
to 95F(35C).
The relative humidity must be held between 5 and 95%. There must be no
condensation due to temperature changes.
This equipment must not be applied at altitude that exceeds 2250m(7400ft)
above seal level.
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust shoud not include iron particles,
oils or fats, or organic materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
MITSUBISHI ELECTRIC 2033G SERIES UPS
Environment standard
No more than 0.003 PPM
)
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM
Page Number:
1-3