Table 1.1 Ups Installation Environment - Mitsubishi Electric 9800A Owner Technical Manual

9800a series uninterruptible power supply system
Hide thumbs Also See for 9800A:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate
insulation, shorten component life and cause malfunctions.
Keep the installation environment per standard described
TABLE 1.1
UPS Installation Environment
No.
Item
1
Installation
Indoors
location
2
Ambient
Minimum temperature: 32F(0C), Maximum temperature: 104F(40C) The
temperature
average temperature over any 24-hour period must be in the range 41 F (5C)
to 95F(35C).
3
Relative
The relative humidity must be held between 5 and 95%. There must be no
humidity
condensation due to temperature changes.
4
Altitude
This equipment must not be applied at altitude that exceeds 2743m(9000ft)
above seal level.
5
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust shoud not include iron particles,
oils or fats, or organic materials such as silicone.
6
Inflammable gas
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NO
Ozone (O
Hydrochloric acid mist (HCl)
MITSUBISHI ELECTRIC 9800A SERIES UPS
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 3
Environment standard
S)
2
)
2
)
2
)
3
)
2
)
x
)
3
Page Number:
1-3
as follows:
No more than 0.0001 PPM
No more than 0.05 PPM
No more than 0.002 PPM
No more than 0.1 PPM
No more than 0.02 PPM
No more than 0.02 PPM
No more than 0.002 PPM
No more than 0.1 mg/m
3