WARNING
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation,
shorten component life and cause malfunctions.
Keep the installation environment per standard described as follows:

Table 1.1 UPS Installation Environment

No.
Item
1
Installation
Indoors
location
2
Ambient
Minimum temperature: 32 F(0 C), Maximum temperature: 104 F(40 C)
temperature
The average temperature over any 24-hour period must be in the range
41 F (5 C) to 95 F(35 C).
3
Relative
The relative humidity must be held between 5 and 95%. There must be
humidity
no condensation due to temperature changes.
4
Altitude
This equipment must not be applied at altitude that exceeds 2220m
(7400ft) above sea level.
5
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron
particles, oils or fats, or organic materials such as silicone.
6
Inflammable
There should be no inflammable/explosive gas.
gas
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NO
Ozone (O
Hydrochloric acid mist (HCl)
1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 3
Environment standard
S)
2
)
2
)
2
)
3
)
2
)
x
)
3
MITSUBISHI ELECTRIC 1100 SERIES UPS
Page Number:
1-6
No more than 0.0001 PPM
No more than 0.05 PPM
No more than 0.002 PPM
No more than 0.1 PPM
No more than 0.02 PPM
No more than 0.02 PPM
No more than 0.002 PPM
No more than 0.1 mg/m
3