Operation

Section 3: Operation

Site Prep Verification

DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
Generator must be installed to allow unim-
peded airflow into and out of generator.
Mechanical and gravity outdoor air intake
openings for air distribution and supply sys-
tems must be located not less than 10 ft
(3.05 m) horizontally from generator enclo-
sure. See Section 401.4 in the ICC Mechani-
cal Code for additional information.
Verify all shrubs or tall grasses within 3 ft
(0.91 m) of intake and discharge louvers on
the sides of the enclosure have been
removed. Install generator on high ground
where water levels will not rise and endanger
it. This unit must not operate in or be sub-
jected to standing water. Verify all potential
water sources such as water sprinklers, roof
run-off, rain gutter downspouts, and sump
pump discharges are directed away from
unit.

Generator Enclosure

Enclosure lid is locked prior to shipment. A
set of keys is attached to cardboard on top of
generator. An additional set of keys is
attached to pallet bracket on the front intake
end of generator.
NOTE: Keys provided with this unit are
intended for service personnel use only.

Opening the Lid

1.
Use keys to open generator lid.
2.
See
3-1. Two locks (A) secure lid;
Figure
one on each side. Open protective rubber
cap to access keyhole.
A
A
Figure 3-1. Opening the Lid
13
3.
Press down on lid above side lock, and
unlock latch to correctly open lid.
4.
Repeat for other side. Lid may appear
stuck if pressure is not applied from the
top.
NOTE: Always verify side locks are unlocked
(000191)
before attempting to lift lid.

Front Access Panel Removal

See
Figure
(A) by lifting straight up and out once lid is
open.
A
Figure 3-2. Remove Front Access Panel
NOTE: Always lift front access panel straight
up before pulling away from enclosure (B and
C). Do not pull panel away from the enclosure
before lifting up (D).
009209
Owner's Manual for 60 Hz Air-Cooled Generators
3-2. Remove front access panel
B
C
D
009210