Trane Precedent THJ072A Installation, Operation And Maintenance Manual page 41

Packaged rooftop air conditioners
Table of Contents

Advertisement

Table 6. Temperature vs. resistance
Temperature
Degrees °F
Degrees °C
-20
-28.9
-15
-26.1
-10
-23.3
-5
-20.6
0
-17.8
5
-15.0
10
-12.2
15
-9.4
20
-6.7
25
-3.8
30
-1.1
35
1.7
40°
4.4
RT-SVX074A-EN
Nominal Resistance
(kOhms)
170.1
143.5
121.4
103.0
87.56
74.65
63.80
54.66
46.94
40.40
34.85
30.18
26.22
Table 6. Temperature vs. resistance (continued)
Temperature
Degrees °F
Degrees °C
45°
7.2
50°
10.0
55°
12.8
60°
15.6
65°
18.3
70°
21.1
75°
23.9
80°
26.7
85°
29.4
90°
32.2
95°
35.0
Installation
Nominal Resistance
(kOhms)
22.85
19.96
17.47
15.33
13.4
11.89
10.50
9.297
8.247
7.330
6.528
41