Troubleshooting - Huawei SUN2000-50KTL-ZHM3 User Manual

Hide thumbs Also See for SUN2000-50KTL-ZHM3:
Table of Contents

Advertisement

SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Check Item
Clear
vegetation
around the
inverters

8.3 Troubleshooting

Alarm severities are defined as follows:
Table 8-2 Common fault alarm list
ID
Name
2001
High
string
input
voltage
Issue 03 (2022-08-30)
Check Method
● Perform inspection and weeding as
required.
● Clean the site promptly after
weeding.
Major: The inverter is faulty. As a result, the output power decreases or the
grid-tied power generation is stopped.
Minor: Some components are faulty without affecting the grid-tied power
generation.
Warning: The inverter works properly. The output power decreases or some
authorization functions fail due to external factors.
Severity
Cause
Major
The PV array is not
properly configured.
Excessive PV modules are
connected in series to the
PV string, and therefore the
PV string open-circuit
voltage exceeds the
maximum inverter
operating voltage.
● Cause ID 1: PV strings 1
and 2
● Cause ID 2: PV strings 3
and 4
● Cause ID 3: PV strings 5
and 6
● Cause ID 4: PV strings 7
and 8
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Maintenance
Interval
Based on the local
wilting season
Solution
Reduce the number of PV
modules connected in series to
the PV string until the PV string
open-circuit voltage is less than
or equal to the maximum
inverter operating voltage. After
the PV string configuration is
corrected, the alarm disappears.
64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-50ktl-m3Sun200050ktl-zhm3-50ktl-m301075485-058

Table of Contents