Vemer ADR-D 230 D22 SPOT User Manual page 2

Single-phase network analyzers

Advertisement

Available languages

Available languages

V3IS00383-010
ADR-D 230 D22 SPOT
Mod.
ADR-D 230 D22 MODBUS
Mod.
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: info@vemer.it - web site: www.vemer.it
Dimensions
65.3
53.7
Connection diagram
I
= 22,5A
MAX
LOAD
LOAD
V
= 300V
V
= 300V
MAX
MAX
50-60 Hz
50-60 Hz
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
-
-
+
+
10 11
12
13
14
15
16
17 18
10 11
12
13
14
15
16
RS-485
(For MODBUS model only)
RS-485
Solo modello MODBUS
model SPOT and MODBUS
model MODBUS
Description
User Manual
SINGLE-PHASE NETWORK ANALYSER
Read all instructions carefully
A series of single-phase system analysers for TRMS (True Root Mean Squared) values:
-
ADR-D 230 D22 SPOT for direct connection of current leads having I
-
ADR-D 230 D22 MODBUS with serial output RS 485 for both direct connection of current
leads having I
= 22,5A and current connection by way of external ATs type x/5A
MAX
SAFETY INSTRUCTIONS
To guarantee correct installation, observe the following instructions:
1) The instrument must be installed by a qualified person
2) The instrument must be installed in an electrical panel which, after installation, leaves
terminals inaccessible
3) The building in which the instrument is installed must have an electrical system
including a switch or a circuit breaker: this must be near the device and in a position
that can be easily reached by operators.
4) A protection device against over-currents must be installed in the electrical system
upstream of the instrument
5) Connect the instrument as shown in the diagrams of this manual
6) Before making contact with terminals, ensure that leads to be connected to the
instrument are not live
7) Do not power or connect the instrument if any part of it is damaged
Note: The network analysers in the ADR-D 230 D22 series are aimed for use in places with
overvoltage category III and pollution degree 2 to EN 61010-1.
Code
Model
Description
VE008900
ADR-D 230 D22 SPOT
Single-phase network analyser
VE009700
ADR-D 230 D22 MODBUS
Single-phase network analyser
TECHNICAL SPECIFICATIONS
Power supply: 230V AC (-15%/+10%) 50/60Hz
Input voltage: V
= 300V
MAX
Input Current:
I
= 5A; I
= 22,5A by direct connection
b
MAX
= 6A by external ATs type x/5A (for MODBUS model only)
I
= 5A; I
n
MAX
Maximum cross-section of current leads: 4 mm
2
Maximum consumption (device only): voltage circuit < 2,5 VA
power circuit < 2,5 VA
power supply < 4 VA
Quantities measured: Voltage (Page 1)
I
= 1000A
Current (Page 2)
MAX
Active power (Page 3)
Power factor (Page 4)
Frequency (Page 5)
Active power (Pages 6-7-8)
8
9
Operating temperature: -10 ÷ +45 °C
Relative humidity: 10% ÷ 90% non-condensing
I -
I +
1
1
Storage temperature: -20 ÷ +60 °C
Signalling leds:
green = power on
red = tx/rx activity on RS 485 line (for MODBUS model only)
Serial output: RS 485 by modbus protocol RTU (for MODBUS model only)
Display: LCD display 7 + 5 digit
17 18
Enclosure: 3 DIN, RAL 7035 gray
Protection rating: IP20/IP51 on the front
ACCURACY
Alternating voltage:
Maximum reading: 105% V
MAX
Minimum reading: 10V
Resolution: 0,1V
Accuracy: ± 0,5% full scale ± 1 digit (full scale: V
Alternating current (automatic scale change):
Maximum reading: 105% I
MAX
Minimum reading: 0,02A
Resolution: 0,01A (range: 0
÷ 100A
) o 0,1A (range: 100
Accuracy: ± 1% full scale ± 1 digit (full scale: 1A)
Accuracy: ± 0,5% full scale ± 1 digit (full scale: 6A)
Accuracy: ± 0,3% full scale ± 1 digit (full scale: 22,5A)
Active power:
Resolution: 0,01kW (range: 0
÷ 100kW
) o 0,1kW (range: 100
Accuracy: ± 1% full scale ± 1 digit (full scale: 100kW o 1000kW)
Power factor:
Resolution: 0,01
Accuracy: ± 1% ± 1 digit
Frequency:
Resolution: 0,1Hz
Accuracy: ± 0,1Hz (from 45Hz to 65Hz)
Total active energy:
Resolution: 1kWh
Accuracy: class 1 to EN 62053-21
Partial active power:
Resolution: 0,01kWh (full scale: 999,99 kWh) or 0,1kWh (full scale: 9999,9 kWh)
Accuracy: class 1 to EN 62053-21
DEVICE DESCRIPTION
Backlit LCD display to read the values measured
Terminals 10-11 for serial output RS 485 (for MODBUS model only)
Terminals 1-3 for the connection of power supply, 5-8-9 for connection of voltage and
current conductors
Green LED: ON when the instrument is powered
Red led (for MODBUS model only): tx/rx activity on RS 485 line
Page scroll button, zeroing of partial meter, parameter set-up
OPERATION
The values measured are read over 6 pages to be scrolled using the SEL button
Total active energy meter
Page 1
Alternating voltage value
= 22,5A
MAX
Total active energy meter
Page 2
Alternating current value
Total active energy meter
Page 3
Active power value
Total active energy meter
Page 4
Power factor value and phase shift type
L = inductive phase shift - C = capacitative phase shift
Page 5
Frequency value
Total active energy meter
Page 6
Partial active energy meter
To access the 2 pages reading active energy counts, press the SEL button again.
Non-zeroable total active energy meter
Page 7
Pagina 8
Zeroable partial active energy meter
The partial meter is automatically zeroed when the scale range is overrun. To set the meter to
zero manually, hold the "SEL" key down for more than 3 seconds
To view the first page again, press the SEL key once more.
BACKLIGHTING
The device's display backlights when the SEL key is pressed: it stays on for 30 seconds after the
last key is pressed.
)
To change this setting, go to page 1 and hold down the SEL key for at least 3 seconds
MAX
Backlighting status (ON / OFF)
÷ 1000A
)
SETUP OF EXTERNAL ATs (for MODBUS model only)
÷
1000kW)
To view the AT setting, go to page 2 and hold down the SEL key for at least 3 seconds.
Current AT value
To change the AT setting, proceed as follows.
Hold the SEL key down while switching the device on: the display will read in a sequence the
firmware version, the serial number and will flash the AT primary value. To select an AT different
than the flashing value, press the SEL key repeatedly until the desired value appears.
The AT values available are as follows: 5/5A, 10/5A, 25/5A, 50/5A, 75/5A, 100/5A, 125/5A, 150/5A,
200/5A, 250/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A.
To effect the change, select the AT value and then press the SEL key until the value stops
flashing. The partial energy count will then be zeroed and the voltage page (page 1) will appear
on the display.
Note: If direct connection of current leads is used (I
value) in the AT setting.
SERIAL-COMMUNICATION CONFIGURATION (for MODBUS model only)
The following serial-communication parameters can be accessed: address number, baud rate and
parity.
To read the current serial parameters, go to page 3 and hold the SEL key pressed for at least
3 seconds, until the address page appears. To scroll the other pages push the SEL key: after
viewing the last page the display resumes normal reading.
To set a parameter, go to the relevant page, hold the SEL key pressed until the value flashes,
press it again to change it and then confirm by pressing it long, until the value stops flashing.
OPERATING MESSAGES
PHASE ERROR
On startup the device checks whether the current and voltage terminals are connected correctly.
In case of error the phase error page will be displayed for 3 minutes. The triangular LED on the
left will flash.
To resume correct operation, turn it off, invert voltage or current connections, and turn on
again.
Error conditions occurring during normal operation are indicated by the flashing of the
triangular LED on the left. Voltage, current and frequency values are nonetheless read correctly.
As for the remaining pages, energy counts will not increase, the power factor will be force-set to
1 and the active power value to 0.
OVERFLOW ERROR
When the voltage or current reading range is overrun, the relevant field will flash dots and the
total energy count will be read.
Voltage or current overflow error is indicated on the other pages too. in this case the values
measured will flash.
SERIAL COMMUNICATION
The instrument (MODBUS model only) has an insulated serial output RS 485.
The data communication system is based on MODBUS protocol (RTU coding system) and can
be connected to a Master system (PC/PLC)...) on a multipoint line RS 485:
- up to 31 ADRs (slaves) without signal amplifiers, from a maximum distance of 1000m
- up to 247 ADRs (slaves) in groups of 30 separated by proper signal amplifiers
Contact the technical assistance service dept. to request documents regarding MODBUS
functions, use of registers and the ADR-view software.
REFERENCE STANDARDS
Conformity to EU directives:
73/23/EEC amended by 93/68/EEC (Low Voltage Electrical Equipment)
89/336/EEC amended by 92/31/EEC and 93/68/EEC (E.M.C.)
is declared with reference to the following harmonised standards:
EN 61010-1, EN 61000-6-2 and EN 61000-6-3
EN 62053-21 and EN 62052-11
= 22,5A), select 5/5A (default
MAX
Assigned address
options: 1 ÷ 247
factory-set value: 1
Baud rate setting
options: 1200, 2400, 4800, 9600
factory-set value: 9600
Parity bit setting
options: none, odd, even
factory-set value: 10 mV/% R.H.
Error reading on start-up
Voltage value with Phase error LED
Voltage page for V > 105% V
MAX