Identification and Overview
BAPI's ZPM is designed for quick
and easy field installation. The
outputs, ranges, units, directionality,
are all easily set in the field without
powering the unit.
The optional LCD display helps with
troubleshooting because it displays
the actual pressure regardless
of the selected pressure range.
Three LEDs on the face of the unit
indicate when the pressure is "Out
of Range Low", "In Range" or "Out
of Range High" for the selected
range. The appropriate LED will
flash when out of range.
Switch Setup - Outputs, Ranges, Units/Response
NOTE! Always follow the Auto-Zero procedure after changing settings.
Fig 2: Setup
Switches for
Standard
Range Units
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
Standard Range ZPM - Zone Pressure Sensor
1. Select OUTPUT
in a BAPI-Box Enclosure
Bulkhead fitting
Static probe
for static probe
screws
Mounting
screws
Deadhead
tubing
Fig. 1: ZPM
BAPI-Box Unit and
Associated Parts
2. Select RANGE
If unit is ordered with a Custom Range,
then the switch must be set to R6.
3. Choose DIRECTION
Bidirectional is a plus/minus range so
choosing 5" range is -5" to +5" Bidirectional
and 0" to +5" Unidirectional
4. Choose UNITS - Inches WC or PASCALS
5. Choose RESPONSE TIME
Fast Response = 1/2 second
Slow Response = 4 seconds
6. Mount, Terminate and Auto-Zero the unit as
described in later sections.
Installation & Operations
rev. 04/13/22
Cover latch
Conduit
screws
foam plug
Static probe
and tube
with surge
damper
(for units
ordered with
the included
static probe)
1 of 5

Advertisement

loading

Summary of Contents for BAPI ZPM Series

  • Page 1 Standard Range ZPM - Zone Pressure Sensor in a BAPI-Box Enclosure Installation & Operations 47138_ins_ZPM_SR_BB rev. 04/13/22 Identification and Overview BAPI’s ZPM is designed for quick Bulkhead fitting Static probe Cover latch Conduit and easy field installation. The for static probe...
  • Page 2 If a hole must be cut into the plastic plugs in the ½” NPSM threaded ports of the BAPI-Box enclosure, it’s recommended to use BAPI’s Clean-Cut Tool. Not using this tool could cause damage to the electronics of the sensor. See the Accessories section of BAPI’s website or product catalog for more info on...
  • Page 3: Mounting Template

    ZPM unit Fig. 6: Mounting Hole Template - shown actual size (BAPI recommends creating 5/32” (4mm) pilot holes for the #10x3/4” self-tapping mounting screws.) Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com...
  • Page 4: Output Termination

    Installation & Operations 47138_ins_ZPM_SR_BB rev. 04/13/22 Output Termination BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty.
  • Page 5: Typical Applications

    Standard Range ZPM - Zone Pressure Sensor in a BAPI-Box Enclosure Installation & Operations 47138_ins_ZPM_SR_BB rev. 04/13/22 Typical Applications NOTE: Best practice is to form a drip loop in the tubing to prevent condensation from reaching the unit. Fig. 10: Duct Static Pressure Monitoring Fig.