BAPI VOC Installation And Operating Instructions Manual

Room sensor in the bapi-stat 3 enclosure with differential ground configuration

Advertisement

Quick Links

29156_ins_voc_room_dif_gnd
Identification and Overview
Humans exhale Volatile Organic Compounds (VOCs) as well
as CO
. The BAPI sensor is able to measure these VOCs,
2
therefore it is as good an indicator of space occupancy as a CO
sensor.
The BAPI Sensor is different from other VOC sensors because
it has been optimized for Demand Controlled Ventilation (DCV).
Using a calibration algorithm, the sensor value is converted to
an output with a high correlation to a CO
use ASHRAE's occupancy-based VRP schedule to ventilate.
(More information on this correlated output is available on our
website at www.bapihvac.com)
The sensor also picks up VOCs from other sources such as
building materials, perfumes, colognes and furniture off-gassing.
Using this sensor to ventilate is a way of achieving true indoor
air quality and not just CO
The unit is available as a VOC sensor alone or in combination
with temperature and humidity. The optional display alternates
between the measured values and is field adjustable between
°F and °C. An optional three color LED indicates a "VOC Level"
of Good, Fair or Poor.
Specifications
Power: (No AC Power)
0 to 5 VDC Output Units:
9 to 35 VDC @ 50 mA Max (9 to 15 VDC recommended)
0 to 10 VDC Output Units:
15 to 35 VDC @ 50mA Max (15 VDC recommended)
Sensing Elements:
Humidity: Capacitive Polymer, ±2% RH Accuracy
VOCs: Micro-machined Metal Oxide
Temp Sensor: Thermistor, RTD or Semiconductor
Mounting: 2"x4" J-Box or drywall mount – screws provided
VOC Detection Range: 0 to 2,000 CO
Response Time: Less Than 60 Sec. (after Start-Up Time)
Start-Up Time: 15 minutes
Operating Environment:
32 to 122°F (0 to 50°C)
0 to 95% RH non-condensing
LCD Display:
Main Display: 0.76" 4-digit Numeric (Numeric Values)
Minor Display: 0.34" 3-digit Alpha-Numeric (PPM, %RH, °F, °C)
Occupied/Unoccupied BAPI Man Icon: (Blk=Occupied)
Note: The VOC contaminant output (CO
for use in an ASHRAE Standard 62.1 Demand Control Ventilation algorithm. The display shows contamination to an
equivalent 5,000ppm CO
2
large VOC contamination when the transmitted output is at its maximum value
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
VOC Room Sensor in the BAPI-Stat 3 Enclosure
level. This lets you
2
dilution.
2
PPM equivalent
2
/VOC terminal on the circuit card) is scaled for 0 to 2,000ppm equivalent CO
2
. This allows additional troubleshooting for a building manager to determine if there is a very
Specifications subject to change without notice.
with Differential Ground Configuration
2
Optional
3-Color LED
Fig 1: BAPI-Stat 3 Room VOC Sensor
Measurement Offsets (field adjustable)
±5° (F or C) in 0.1° increments
±5% RH in 0.1% RH increments
±5% Contaminants in 0.1% increments
±100 ppp CO
ments
Analog Outputs
(0 to 5, 0 to 10 or 2 to 10VDC [%RH only], >10KΩ impedance)
VOC Contaminants: 0 to 2,000 CO
%RH: 0 to 100% or 35 to 70% RH
Override Output:
Contact: SPST
Sensor: Shorts out direct Temperature sensor (Temp)
Setpoint: Contact in parallel, resistive setpoint only
LED CO
Equivalent Level Indicator:
2
Good, Green < 1,000 PPM
Fair, Yellow = 1,000 to 1,500 PPM
Poor, Red > 1,500 PPM
Material: ABS Plastic, Material Rated UL94V-0
Certifications: RoHS
Warranty Period: 5 years from manufacture date
Installation and Operating Instructions
with Optional 3-Color LED
Equivalent Contaminants in 2 ppm incre-
2
PPM equivalent
2
rev. 06/05/18
2
1 of 8

Advertisement

Table of Contents
loading

Summary of Contents for BAPI VOC

  • Page 1 Warranty Period: 5 years from manufacture date Note: The VOC contaminant output (CO /VOC terminal on the circuit card) is scaled for 0 to 2,000ppm equivalent CO for use in an ASHRAE Standard 62.1 Demand Control Ventilation algorithm. The display shows contamination to an equivalent 5,000ppm CO .
  • Page 2: Junction Box

    The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction box, filling the junction box with fiberglass insulation or sealing the wall cavity.
  • Page 3: Terminal Function

    All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show fluctuating and inaccurate signals are possible when AC power wiring is in the same conduit as the signal lines.
  • Page 4: User Operation

    Commissioning Fig 6: Optional Display The display indicates VOC in PPM, air temperature in degrees Fahrenheit or Celsius, relative humidity in %RH, temperature setpoint in degrees Fahrenheit or Celsius and override using the BAPI Man icon. The three arrow icons are used with the –ARW option to show VOC levels and their meaning.
  • Page 5: Optional Technician Adjustments

    Some installations may experience erratic temperature readings. A possible remedy may be to float the temperature sensor as shown in Figs 8 and 9. Run wires directly from TP+ and TP- to the controller’s analog input. The VOC/CO2 Fig 8: Temp.
  • Page 6: Output Selection

    B. Wait four minutes fifteen seconds. C. The VOC sensor will set the VOC output voltage to 5% of full scale (0.25 VDC for 0 to 5 VDC, 0.5 VDC for 0 to 10 VDC or 2.4 VDC for 2 to 10 VDC outputs). Display units will illuminate the ON icon and set the main display to 1.0.
  • Page 7 3. Termination of Verification Mode A. For the last 7 minutes of the start-up period the sensor adapts to its ambient environment. The VOC sensor will maintain its output voltage at 450 ppm CO2 equivalent. Display units will show 450 ppm equivalents.
  • Page 8 BAPI website. (Go to www.bapihvac.com; click on “Resource Library” and “Sensor Specs”, then click on the sensor type you have.) If the measured resistance is different from the temperature table by more than 5% call BAPI technical support. Don’t forget to reconnect the wires.