Identification and Overview
The BAPI CO
Duct Sensor is an accurate and reliable way
2
of incorporating demand controlled ventilation. It measures
CO
in ranges of 0 to 2,000, 0 to 5,000, 0 to 10,000 and 0
2
to 50,000 ppm with a field selectable output of 0 to 5 or 0 to
10 VDC.
The Single Beam (ACD) unit has been optimized for
periodically unoccupied areas and features automatic
background calibration over a long time period to reduce
drift. The Dual Channel (DCD) "24/7" unit has been
optimized for continuously occupied areas and features a
3-point calibration process.
Three-color
LED

Specifications

Power:
12 to 24 VDC, 240mA
18 to 24 VAC, 12 VA Peak
CO
Sensing Elements:
2
Single Beam Non-Dispersive Infrared (NDIR)
or Dual Channel NDIR for "24/7" Model
Selectable Output:
0 to 5 VDC or 0 to 10 VDC
Termination: 3 Terminals, 16 to 22 AWG
Wiring: 2 Pair
Operating Environment:
32 to 122°F (0 to 50°C)
0 to 95%RH non-condensing
Enclosure Material:
Polycarbonate, UL94 V-O
CO
Detection Range:
2
0 to 2,000, 0 to 5,000, 0 to 10,000 and 0 to 50,000 ppm
Start-Up Time: 10 Minutes
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
CO
Fig. 1: Duct CO
Sensor
2
Specifications subject to change without notice.
Duct and Rough Service Sensor
2
Installation & Operating Instructions
Barometric pressure changes from altitude or weather
can affect CO
sensors, even putting them outside of their
2
specified accuracy. The BAPI unit has a built-in Barometric
pressure sensor that continuously compensates the output
for accurate readings despite the weather or altitude.
The Duct unit samples duct air using an aspiration tube.
The Rough Service unit features a ventilated BAPI-Box and
is ideal for areas such as outdoor air plenums, equipment
rooms, attics, green houses and warehouses. Optional
indication of the CO
2
available as a 3-color LED for 0 to 2,000 ppm range units.
Fig. 2: Rough Service CO
Response Time:
Less Than 5 Minutes (after Start-Up Time)
CO
Accuracy:
2
(Automatic Background Calib. Single Channel Model)
400 to 1,250 ppm: ±30ppm or 3% of reading,
1,250 to 2,000 ppm: ±5% of reading + 30ppm
CO
Accuracy:
2
("24/7" Dual Channel Model)
75ppm or 10% of reading (whichever is greater)
CO
Drift Stability (DCD "24/7" Units):
2
<5% of full scale over life of product.
Optional 3-Color LED (0 to 2,000 ppm range only):
Good, Green < 1,000 PPM CO
Fair, Orange = 1,000 to 1,500 PPM CO
Poor, Red > 1,500 PPM CO
Certifications: RoHS
Warranty Period:
5 Years from manufacture date
level as "Good, Fair or Poor" is
2
whichever is greater
2
2
2
rev. 08/21/17
Sensor
1 of 4

Advertisement

loading

Summary of Contents for BAPI CO2 Duct

  • Page 1: Specifications

    0 to 2,000, 0 to 5,000, 0 to 10,000 and 0 specified accuracy. The BAPI unit has a built-in Barometric to 50,000 ppm with a field selectable output of 0 to 5 or 0 to pressure sensor that continuously compensates the output 10 VDC.
  • Page 2 “Resource Library” from the banner. Click on “Application Notes” then scroll down the page to the heading “Air Quality Related” and chose “Coverage Area and Mounting Recommendations for BAPI Indoor Air Quality Sensors”. 1. BAPI recommends #10 (M5) screws of a type and length suitable for the mounting surface. Four mounting screws keeps the box from twisting, twisting may prevent the latch from operating properly.
  • Page 3 All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines.
  • Page 4 This draft may prevent the unit from measuring ambient CO . BAPI recommends either a liquid-tight fitting or plugging the conduit at the enclosure. • Liquid-Tight Fitting – BAPI’s Liquid-Tight Fitting (BA/LTF) allows wire Fig.

This manual is also suitable for:

Rough