Identification and Overview
The BAPI CO
Sensor is an accurate and reliable way of incorporat-
2
ing demand controlled ventilation into a building's HVAC strategy. It
measures the CO
in a range of 0 to 2,000 ppm with a field selectable
2
output of 0 to 5 or 0 to 10 VDC.
The non-dispersive infrared (NDIR) technology has been optimized
to reduce drift. The sensor is also altitude compensated for long-
term accuracy and stability. Changing air pressure, due to altitude
or weather patterns, can change the output of most CO
as much as 17%. The BAPI unit has a built-in barometric sensor that
continuously compensates the output for accurate readings despite
inclement weather or the altitude of the installation.
The unit can be ordered as CO
sensing, temperature setpoint, occupant override and humidity sens-
ing. The large format display is easy to read and alternates between
the measured values (CO
also field adjustable between °F or °C and all the displayed values
may be turned on or off by an HVAC technician.
Optional indication of the CO
able as a three-color LED on the unit or as an arrow on the display.
Specifications
Power for 0 to 5 VDC Outputs:
9 to 35 VDC @ 240mA (9 to 24 VDC recommended)
Power for 0 to 10 VDC Outputs:
15 to 35 VDC @ 240mA (15 to 24 VDC recommended)
Sensing Elements:
CO
– Single Beam Non-Dispersive Infrared (NDIR)
2
or Dual Channel NDIR for "24/7" Model
Humidity – Capacitive Polymer ±2% RH Accuracy
Temperature Sensor:
Thermistor, RTD or Semiconductor
Operating Environment:
32 to 122°F (0 to 50°C)
0 to 95%, RH non-condensing
Material ABS Plastic, Material Rated UL94V-O
CO
Detection Range: 0 – 2000 ppm
2
Start-Up Time: <2 Minutes
Response Time:
<2 Minutes for 90% step change typical (after start-up)
Mounting: 2"x4" J-Box or drywall – screws provided
Override Output:
Contact ....SPST, 24V AC/DC, 0.5A max
Sensor .....Shorts Out direct temperature sensor
Setpoint ...Contact in parallel, resistive setpoint only
CO
Room Sensor in the BAPI-Stat 3 Enclosure
2
with Common Ground Configuration
alone, or with optional temperature
2
, Temperature or Humidity). The display is
2
level as "Good, Fair or Poor" is avail-
2
Specifications subject to change without notice.
Installation and Operating Instructions
sensors by
2
Fig. 1: BAPI-Stat 3 Room CO
LCD Display:
Main Display: 0.76" 4-digit Numeric Values
Minor Display: 0.34" 3-digit Alpha-Numeric
(PPM, %RH, °F, °C)
Occupancy BAPI Man Icon: (Blk=Occupied)
Measurement Offsets: (Field Adjustable)
±5° (F or C) in 0.1° increments
±5% RH in 0.1% RH increments
CO
Accuracy:
2
(Single Channel Automatic Background Calibration model)
400 to 1,250 ppm: ±30ppm or 3% of reading,
1,250 to 2,000 ppm: ±5% of reading + 30ppm
CO
Accuracy: ("24/7" Dual Channel Model)
2
75ppm or 10% of reading (whichever is greater)
CO
Drift Stability (Dual Channel DCD "24/7" Units):
2
<5% of full scale over life of product.
LED CO
Level Indicator:
2
Good, Green < 1,000 PPM
Fair, Orange = 1,000 to 1,500 PPM
Poor, Red > 1,500 PPM
Certifications: RoHS
Warranty Period: 5 Years from manufacture date
2
whichever is greater
rev. 04/27/18
Sensor
1 of 6

Advertisement

loading

Summary of Contents for BAPI CO2

  • Page 1 CO sensors by as much as 17%. The BAPI unit has a built-in barometric sensor that continuously compensates the output for accurate readings despite inclement weather or the altitude of the installation.
  • Page 2: Junction Box

    The mixing of room air and air from within the wall cavity can lead to condensation, er- roneous readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction box, filling the junction box with fiberglass insulation or sealing the wall cavity.
  • Page 3 All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show fluctuating and inaccurate signals are possible when AC power wiring is in the same conduit as the signal lines.
  • Page 4: User Operation

    The display indicates CO in PPM, temperature in °F or °C, %RH, temperature setpoint in degrees °F or °C and override BAPI Man using the BAPI Man icon. The three triangle icons are used Icon with the –ARW option to show CO levels.
  • Page 5: Optional Technician Adjustments

    Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration Installation and Operating Instructions 26141_ins_room_CO2 rev. 04/27/18 Optional Technician Adjustments BAPI’s CO room sensor comes calibrated and ready to operate. In some installations the sensor may not match local instrumentation. The technician adjustment procedure allows °F or °C display units, temperature or humidity...
  • Page 6: Output Selection

    Compare the temperature sensor’s resistance to the appropriate temperature sensor table on the BAPI website. (Go to www.bapihvac.com; click on “Resource Library” and “Sensor Specs”, then click on the sensor type you have.) If the measured resistance differs from the temperature table by more than 5%, call BAPI technical support.