Zone pressure sensor

Advertisement

Quick Links

38926_ins_ZPM_LR
Identification and Overview
BAPI's ZPM is designed for quick
and easy field installation. The
outputs, ranges, units, directionality,
and response time are quickly set in
the field with no tools, no power and
no small components.
The optional LCD display helps with
troubleshooting because it displays
the actual differential pressure
over the entire operational range
regardless of which pressure range
is selected for output to the system
controller. Three LEDs on the
face of the unit indicate when the
pressure is "Out of Range Low", "In
Range" or "Out of Range High".
Switch Setup - Outputs, Ranges, Units/Response
Do not have power applied to unit when changing settings. After changing settings, apply power and Auto-Zero
the unit in its orientation of operation.
Fig 2: Setup
Switches for
Low Range
Units
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
Low Range ZPM - Zone Pressure Sensor
1. Select OUTPUT
Specifications subject to change without notice.
Bulkhead fitting
Static tube
for static tube
screws
Mounting
screws
Deadhead
tubing
Fig. 1: ZPM unit and
associated parts
2. Select RANGE
If unit is ordered with a Custom Range,
then the switch must be set to R6.
3. Choose DIRECTION
Bidirectional is a plus/minus range so
choosing 0.5" range is -0.5" to +0.5"
Bidirectional and 0" to +0.5" Unidirectional
4. Choose UNITS - Inches WC or PASCALS
5. Choose RESPONSE TIME
Fast Response = 1/2 second
Slow Response = 4 seconds
6. Mount, Terminate and Auto-Zero the unit
as described in later sections. Attach
the deadhead tubing to the ports during
Auto-Zeroing
Installation & Operations
rev. 04/09/20
Cover latch
Conduit
screw
foam plug
Static tube
and hose
with surge
damper
(for units
ordered with
the included
Static Tube.)
1 of 4

Advertisement

loading

Summary of Contents for BAPI Low Range ZPM

  • Page 1 Low Range ZPM - Zone Pressure Sensor Installation & Operations 38926_ins_ZPM_LR rev. 04/09/20 Identification and Overview BAPI’s ZPM is designed for quick Bulkhead fitting Static tube Cover latch Conduit for static tube screws screw foam plug and easy field installation. The...
  • Page 2 Low Range ZPM - Zone Pressure Sensor Installation & Operations 38926_ins_ZPM_LR rev. 04/09/20 Mounting Attach the unit to its mounting surface with four self-tapping #10x3/4” sheet metal screws through the holes in the mounting feet. The preferred mounting orientation is with the pressure ports facing down.
  • Page 3 Low Range ZPM - Zone Pressure Sensor Installation & Operations 38926_ins_ZPM_LR rev. 04/09/20 Output Termination BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty.
  • Page 4 Low Range ZPM - Zone Pressure Sensor Installation & Operations 38926_ins_ZPM_LR rev. 04/09/20 Typical Applications Fig. 8: Duct Static Pressure Monitoring Fig. 9: Air Filter Pressure Drop Monitoring (ZPM Pressure Sensor mounted on the duct (ZPM Pressure Sensor mounted on the with a Static Pressure Probe in the duct.)

This manual is also suitable for:

Zpm series