LED Indicators
Output Circuit Status LEDs (red)
Output inactive
Output active
Output Circuit Trouble LEDs (yellow)
No Fault
Fault Condition:
Wire Supervision
Class A or B Open circuit
1 short blink (250ms)
Fault Condition:
Wire Supervision
Class A or B Short Circuit
2 short blinks (250ms)
Fault Condition:
Aux Power Supervision
Class A Open circuit
(ZNAC-PS Circuit #1 and #2 only)
3 short blinks (250ms)
Fault Condition:
Power limit condition (individual ckt overload)
4 short blinks per individual circuit (250ms)
Fault Condition:
Power limit condition (panel overload)
4 short blinks on all output circuits (250ms)
Operating Mode Fault:
Power Supply Change Output Config. Mode
Set positions 9 and 10 on S1 to the correct
position. Refer to "Operating Modes" on
page 26.
Retrofit Mode Indication (yellow)
Retrofit Mode will be
indicated by an LED blink on
the NAC1 Trouble LED only.
NAC outputs fault conditions
will still be indicated by short
250ms blinks (where
applicable).
32
LED is OFF
LED is ON constant
LED is OFF
Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
*Retrofit Mode will be indicated by an LED blink on the NAC1 Trouble LED only
Repeating LED blink pattern (non-diagnostic phase)
Output circuit Trouble LEDs blink from right to left across all output circuits for 500ms.
Repeating LED blink pattern (non-diagnostic phase and diagnostic phase)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022
Retrofit
pause
Mode*
1000ms
1000ms
Retrofit
Mode*
1000ms
1000ms
Retrofit
Mode*
1000ms
1000ms
Retrofit
Mode*
1000ms
1000ms
Retrofit Mode
pause
1000ms
1000ms
pause
pause
pause