DC/DC Converter - 48V/48V, 5 A, 240 W Catalog Number 1606-XLDF240F Reference Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Width only 42 mm (1.65 in.) • 20% output power reserves • Full power between -25…+60 °C (-13…+140 °F) • Soft start function • Minimal inrush current surge • Reverse input polarity protection Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
At 48V, 5 A constant current load, 0 mF load capacitance; 50 ms Figure 2 on page 7 Rise time At 48V, 5 A constant current load, 5 mF load capacitance; 150 ms Figure 2 on page 7 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Line regulation 50 mV Between 36…60V DC input voltage variation Load regulation 200 mV Between 0…5 A load variation, static value Ripple and noise voltage 100 mVpp Bandwidth 20 Hz…20 MHz, 50 Ω Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Figure 13 - Efficiency Versus Input Voltage at 48V, 10 A, Figure 14 - Losses Versus Input Voltage at 48V, 10 A, Typical Typical 95.5 95.0 94.5 94.0 93.5 93.0 Input Voltage (V DC) Input Voltage (V DC) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
At 48V, 5 A, and 25 °C (77 °F); Ground Benign GB25 MTBF MIL HDBK 217F 71 kHz At 48V, 5 A, and 40 °C (104 °F); Ground Fixed GF40 97 kHz At 48V, 5 A, and 25 °C (77 °F); Ground Fixed GF25 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
2) this device must accept any interference received, including interference that can cause undesired operation. (1) Not available at the time of publishing. Switching frequency information is provided in the following table. Attribute Values Notes Main converter 75…500 kHz Dependent on input voltage and output load Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
B... Short term A... Ambient <60 °C B... Ambient <45 °C C... Short term 2000 m 4000 m 6000 m 110 kPa 80 kPa 62 kPa 47 kPa °C) Ambient Temperature ( Altitude (Atmospheric Pressure) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
1500V AC 500V AC Routine test 1500V AC 1500V AC 500V AC Output Field test 1000V AC 1000V AC 500V AC Cutoff current setting — 20 mA 10 mA 12 mA Chassis Ground Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Small parts like screws and nuts with a diameter larger than 3.5 mm (0.14 in.). (1) The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
This bracket mounts the device sideways with or without using a DIN rail to save installation depth. The two aluminum brackets and the black plastic slider of the device must be detached so that the steel bracket can be mounted. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
In times when the DC/DC converter provides sufficient voltages, the buffer module stores energy in integrated electrolytic capacitors. If there is a supply voltage fault, then this energy is released again in a regulated process. 1606-XLSBUFFER Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Ohm’s Law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCB’s magnetically trip depending on the wire cross section and wire length. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Do not use power supplies in series and in mounting orientations other than the standard Output mounting orientation. Electromagnetic interference (EMI) and inrush current increase when you use multiple devices. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Redundant systems for a higher power demand are built in an N+1 method, such as four devices with each rated for 10 A are paralleled to build a 30 A redundant system. EMI and inrush current increase when you use multiple devices. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Temperature inside the box 43.5 °C (110.3 °F) 48.1 °C (118.6 °F) Temperature outside the box 26.2 °C (79.2 °F) 26.6 °C (79.8 °F) Temperature rise 17.3 °C (31.1 °F) 21.5 °C (38.8 °F) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Ambient Temperature ( Figure 31 - Mounting Orientation D (horizontal with input on the left) °C) Ambient Temperature ( Figure 32 - Mounting Orientation E (horizontal with input on the right) °C) Ambient Temperature ( Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
Page 24
DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Notes: Rockwell Automation Publication 1606-RM124A-EN-P - September 2021...
DC Power Supply - 24V, 3.8 A, 90 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Provides guidance on how to conduct security assessments, implement Rockwell Automation System Security Design Guidelines Reference Manual,...
Page 26
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.