DC/DC Converter - 24V/24V,
10 A, 240 W
Catalog Number 1606-XLDD240E
Reference Manual
Original Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLDD240E

  • Page 1 DC/DC Converter - 24V/24V, 10 A, 240 W Catalog Number 1606-XLDD240E Reference Manual Original Instructions...
  • Page 2 If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Table Of Contents

    Additional Resources ..........29 Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 4 Notes: Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 5: Terminology And Abbreviations

    Width only 42 mm (1.65 in.) • 20% output power reserves • Full power between -25…+60 °C (-13…+140 °F) • Soft start function • Minimal inrush current surge • Reverse input polarity protection Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 6: Specifications

    Without DIN rail (1.65 x 4.88 x 4.61 in.) Weight 500 g (1.1 lb) — Catalog Numbers Catalog Numbers Descriptions 1606-XLDD240E DC/DC Converter 1606-XLC Wall or panel mount bracket 1606-XLA-S44 Side mount bracket Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 7: Dc Input

    Figure 3 - Turn-on Behavior, Definitions Rated input range Input Voltage - 5% Output Voltage Start-up Rise delay Time Figure 4 - Input Current Versus Output Load Input 16 A Current, Output Current 12 A Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 8: Requirements For The Supplying Source

    Output: 24V, 10 A, constant current load • Ambient: 25 °C (77 °F) • Input current: 2 A / DIV • Input voltage: 5V / DIV • Output voltage: 5V / DIV • Time basis: 100 ms / DIV Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 9: Soft Start Feature

    24V DC Input Voltage, Typ 23V Constant Voltage Load, Typ Output Current Adjustment Output Voltage Range 14 A 13.5 13.0 12.5 12.0 11.5 11.0 10.5 Input Voltage Output Current 10.0 16 A 36V DC Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 10: Hold-Up Time

    (b): 24V, 5 A, min (c): 24V, 10 A, typ (d): 24V, 10 A, min Input Voltage 28V DC Figure 11 - Shutdown Behavior, Definitions S1 opens Intput Voltage - 5% Output Voltage Hold-up Time Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 11: Efficiency And Power Losses

    Figure 15 - Losses Versus Input Voltage at 24V, 10 A, Typ 10 A, Typ Efficiency Power Losses 19 W 94.5 94.0 93.5 93.0 92.5 Input Voltage Input Voltage 92.0 32V DC 32V DC Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 12: Functional Diagram

    On when the voltage on the output terminals is > 21V Input terminals (screw terminals) + Positive input - Negative / return input Chassis Ground: to bond the Housing to Ground, PE, or Functional Earth Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 13: Connection Terminals

    Figure 18 - Daisy Chaining of Outputs Figure 19 - Using Distribution Terminals 25 A max Output Output Output Output Load Load DC/DC DC/DC DC/DC DC/DC Converter Converter Converter Converter Distribution Input Input Input Input Terminals Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 14: Lifetime Expectancy

    At 10 A and 25 °C (77 °F); Ground Benign GB25 MTBF MIL HDBK 217F 731,000 hr At 10 A and 40 °C (104 °F); Ground Fixed GF40 142,000 hr At 10 A and 25 °C (77 °F); Ground Fixed GF25 Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 15: Electromagnetic Compatibility

    Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Switching Frequency Attribute Values Notes Main converter 50...300 kHz Output load and input voltage dependent Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 16: Environment

    B: Short term B: Ambient < 45 °C C: Short term Ambient Temperature Altitude 2000 m 4000 m 6000 m 110 kPa 80 kPa 62 kPa 47 kPa 70 °C (1) Atmospheric pressure Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 17: Safety And Protection Features

    It is recommended that either the + pole, the – pole or any other part of the output circuit shall be connected to the earth/ground system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 18: Approvals

    Directive 1907/2006/EU of the European Parliament and the Council of June 1, REACH Directive 2007 regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals (REACH) IEC/EN 61558-2-16 Safety Isolating Transformers corresponding to Part 2-6 of the IEC/EN 61558 Safety Isolating Transformer (Annex BB) Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 19: Physical Dimensions And Weight

    Penetration protection Small parts like screws, or nuts with a diameter larger than 3.5 mm (0.138 in.) Figure 23 - Front View Figure 24 - Side View Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 20: Accessories

    Figure 26 - Hole Pattern Figure 27 - Side View All dimensions in mm All dimensions in mm Figure 28 - Right Front View Figure 29 - Left Front View Figure 30 - Right Back View Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 21: 1606-Xla-S44 Side Mount Bracket

    1606-XLA-S44 steel bracket. Figure 31 - Hole Pattern Figure 32 - Side Mount Bracket Figure 33 - Side Mounting Without Figure 34 - Side Mounting With DIN Rail Brackets DIN Rail Brackets Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 22: 1606-Xlered Redundancy Module

    One buffer module can deliver 20 A additional current. Buffer modules can be added in parallel to increase the output ampacity or the hold-up time. Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 23: Peak Current Capability

    At 20 A for 50 ms, resistive load Peak current voltage dips 24V dips to 12V At 40 A for 2 ms, resistive load 24V dips to 6V At 40 A for 5 ms, resistive load Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 24: Output Circuit Breakers

    • Do not use the devices for battery charging in any condition where a reduction of the output current is required, such as mounting orientations other than the standard mounting orientation, or altitude. Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 25: Series Operation

    EMI and inrush current increase when using multiple devices. Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 26: Parallel Use For Redundancy

    Input Input Input Input Output Output Input ok Input ok DC/DC DC/DC Converter Redundancy Converter Redundancy Module Module Input Input Output Output Load Functional Earth Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 27: N+1 Redundancy

    Temperature inside the box 52.2 °C (125.96 °F) 59.3 °C (138.74 °F) Temperature outside the box 31.0 °C (87.8 °F) 31.4 °C (88.52 °F) Temperature rise 21.2 K (38.16 °F) 27.9 K (50.22 °F) Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 28: Mounting Orientations

    Horizontal with Input on the Left +70 °C Ambient Temperature Allowed Output Current at 24V 12 A Figure 46 - Mounting Orientation E: Horizontal with Input on the Right +70 °C Ambient Temperature Rockwell Automation Publication 1606-RM115A-EN-P - September 2020...
  • Page 29: Additional Resources

    DC/DC Converter - 24V/24V, 10 A, 240 W Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Switched Mode Power Supply Specifications Technical Data, publication Provides specifications for Bulletin 1606 products and applications.
  • Page 30 At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.