Mitsubishi Electric PUD-SWM60VAA-BS Service Manual page 46

Table of Contents

Advertisement

Outdoor power circuit board
PUD-SWM80YAA(-BS).UK
PUD-SWM100YAA(-BS).UK
PUD-SWM120YAA(-BS).UK
PUD-SHWM80YAA(-BS).UK
PUD-SHWM100YAA(-BS).UK
PUD-SHWM120YAA(-BS).UK
PUD-SHWM140YAA(-BS).UK
Diode module
TAB connector
on X52CA
Connect to the
RS resistor
TB-L1,
TB-L2,
TB-L3
Connect to the
outdoor converter
circuit board (L1-
OU, L2-OU,
L3-OU)
400 VAC
CN4
Connect to the out-
door controller cir-
cuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1–5: Power circuit board
signal to the controller board (0–5 VDC)
2–5: Zero cross signal (0–5 VDC)
3–4: Not used
[ 5 : –
6–5: 16 VDC
7–5: 16 VDC
OCH694A
Note: The marks L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
TB-N
Connect to the CK capacitor
P1
L1
CN5
Detection of primary
current (Connect to
the outdoor noise filter
circuit board (CNCT))
Transmitting
1, 2, 6, 7 : + ]
Brief Check of POWER MODULE
• If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check of DIODE MODULE
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
shown in the diagram are not actually printed on the board.
N2
L2
L3
N1
CN7
Connect to the
outdoor converter
circuit board (CN7)
CN6
Thermistor
<Heat sink> (TH8)
46
TB-U, TB-V, TB-W
Connect to the compressor (MC)
Voltage among phases:
10–400 VAC
W
V
U
P2
L3OUT-L3IN
Lead connect
DIP-IPM