Mitsubishi Electric PUD-SWM60VAA-BS Service Manual page 23

Table of Contents

Advertisement

Check code
Abnormal point and detection method
63H connector open
Abnormal if 63H connector circuit is open for
3 minutes continuously after power supply.
63H: High pressure switch
F5
(5201)
Indoor/outdoor unit connector
miswiring, excessive number of units (2
units or more)
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically
due to miswiring of indoor/outdoor unit
connecting wire and etc. after power is
turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
EA
board recognizes the number of
(6844)
connected indoor units as "2 units or
more".
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or
disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number cannot
be set within 4 minutes after power on
because of miswiring (converse wiring or
disconnection) of indoor/outdoor unit
Eb
connecting wire.
(6845)
Startup time over
The unit cannot finish startup process with-
in 4 minutes after power on.
EC
(6846)
Incorrect connection
The outdoor unit does not receive the sig-
EE
nals of I/F or FTC.
OCH694A
Cause
1 Disconnection or contact fail-
ure of 63H connector on out-
door controller circuit board
2 Disconnection or contact fail-
ure of 63H
3 63H is working due to defec-
tive parts.
4 Defective outdoor controller
circuit board
1 Contact failure or miswiring of
indoor/outdoor unit connecting
wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
3 2 or more indoor units are
connected to one outdoor unit.
4 Defective transmitting receiving
circuit of outdoor controller
circuit board
5 Defective transmitting receiving
circuit of indoor controller
board
6 Defective indoor power board
7 Do NOT use refrigerant
address 0, as 0 is used for
FTC (Master). The address
range is 1 to 6. (In the case of
multiple outdoor units control.)
8 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
1 Contact failure or miswiring of
indoor/outdoor unit connecting
wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
4 Defective transmitting receiving
circuit of outdoor controller circuit
board
5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board
7 Do NOT use refrigerant
address 0, as 0 is used for
FTC (Master). The address
range is 1 to 6. (In the case of
multiple outdoor units control.)
8 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
1 Contact failure of indoor/
outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
3 Do NOT use refrigerant
address 0, as 0 is used for
FTC (Master). The address
range is 1 to 6. (In the case of
multiple outdoor units control.)
4 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
1 A device other than Interface
unit or Flow temp. controller
unit is connected to the unit.
23
Judgment and action
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to "9-6.TEST POINT DIAGRAM".
2 Check the 63H side of connecting wire.
3 Check continuity by multimeter.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of
indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 80 m
(including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat cable
is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected)
4–6 Turn the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
7 Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board) are
overlapping in the case of multiple outdoor
units control.
8 Check transmission path, and remove the
cause.
Note: The descriptions above, 1–8, are for EA,
Eb and EC.
1 Connect I/F or FTC to the unit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents