8-3. FAN OPERATION
F1
F2
F3
.
Control Mode
1. Temperature
Set by remote controller.
adjustment
function
4 speeds + Auto type
When [Auto] is set, fan speed becomes [Low].
2. Drain pump
2-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the following
conditions has been satisfied:
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (FAN).
2 ON for 6 minutes after the float switch is submerged in the water when the float switch
control judges the sensor is in the water.
2-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the
float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air
3. Vane
Same as the control performed during the COOL operation, but with no restriction on the vane's
(up/down vane
downward blow setting
change)
OCH611D
<How to operate>
1 Press
2 Press [F1] button to display FAN.
F4
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display FAN.
Control Details
Type
Auto
: Detected that the float switch is OFF for 15 seconds.
button.
Fan speed notch
25
Remarks
• Operates as it would
in COOL operation.