The test is passed if the components required for the specified housing degree of protection are
available.
3.1.3

Electrical cabinet components

Fundamentals
A visual inspection is made to see whether the electrical cabinet components are installed as
defined in the layout diagram and/or circuit diagram.
Test procedure
1. The customer selects electrical cabinet components by random sampling.
2. The selected electrical cabinet components are visually checked to ensure that they are
Result
The test is passed if the selected electrical cabinet components are installed as specified in the
layout diagram and/or circuit diagram.
3.1.4

Cable installation

Fundamentals
Visual and mechanical checks are made to ensure that cables and conductors have been
installed correctly and are connected correctly according to the circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
2. The following is inspected:
Result
The inspection is passed if the cable installation does not exhibit any deficiencies and matches
the information in the circuit diagram.
SINAMICS GL150 6SL3855 F03 F70 F76 F79 F98 E11
Reference Manual Rev.201902141423 GL150 wassergekühlt
correctly installed and marked.
– Are the cables firmly connected?
– Have edge protectors been attached to sharp edges?
– Are the cables routed according to the circuit diagram?
Tests
3.1 Visual inspection
19