Service manual
Lambdatronic S 3200 for firewood boiler
Core module version 50.04 - Build 05.20 | Touch control version 60.01 - Build 01.38
Translation of the original German installation instructions for technicians
Read and follow the instructions and safety information!
Technical changes, typographical errors and omissions reserved!
B1420922_en | Edition 27/10/2022
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Lambdatronic S 3200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fröling Lambdatronic S 3200

  • Page 1 Service manual Lambdatronic S 3200 for firewood boiler Core module version 50.04 - Build 05.20 | Touch control version 60.01 - Build 01.38 Translation of the original German installation instructions for technicians Read and follow the instructions and safety information!
  • Page 2: Table Of Contents

    Table of contents 3.4 Starting the setting wizard 1 General 4 Parameters overview 1.1 About these instructions 1.2 Safety information 4.1 Heating 4.1.1 Heating - Status 2 Power connection and wiring 4.1.2 Heating – Temperatures 4.1.3 Heating - Times 2.1 Core module and connection options 4.1.4 Heating - Service 2.1.1 Board view - core module 4.1.5 Heating - Heating up program...
  • Page 3 4.14.4 Diagnostics - Clear error history 7.1 Addresses 4.15 Touchscreen 7.1.1 Address of manufacturer 4.15.1 Touchscreen - Display settings Customer service Display settings - General 7.1.2 Address of the installer Display settings - Basic display Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 4: General

    General About these instructions 1 General 1.1 About these instructions Please read and follow the operating instructions, in particular the safety information contained therein. Keep them available next to the boiler. These operating instructions include important information about operation, electrical connection and troubleshooting.
  • Page 5: Power Connection And Wiring

    Caution! CAN L and CAN H must not be connected to +U KM-02 Patch cable CAT 5 RJ45 SFTP 1:1 configuration; pellet module connection KM-03 KM-04 COM 2 Null modem cable 9-pin SUB-D; Connection is used e.g. as MODBUS interface Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 6 Power connection and wiring Core module and connection options Connection / Name Note KM-05 COM 1 Null modem cable 9-pin SUB-D; Service interface for software update and connection to visualisation software KM-06 Broadband probe Connection cable 5 x 0.75 mm Connection of a Bosch (item number 69001A) or NTK (item number 69003) broadband Lambda probe KM-07...
  • Page 7 ⇨ See "Operating signal" [page 14] KM-36 Optional module Ignition expansion connection 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Fuses 6.3 AT Pump 1, induced draught fan Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 8 Power connection and wiring Core module and connection options Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 9: Mains Connection

    In the delivered state, the outside temperature sensor is read in by the core module ("KM-19 / outside temperature sensor" connection). Alternatively, the outside temperature sensor can be connected to an additional heating circuit module. ⇨ See "Heating circuit module" [page 15] Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 10: Fra Room Temperature Sensor

    Power connection and wiring Core module and connection options 2.1.4 FRA room temperature sensor In addition to recording the current room temperature, the Froling FRA room temperature sensor also has a handwheel to adjust the required room temperature and a slide switch to set the mode for the heating circuit. affecting room: not affecting room: Raumfühler FRA...
  • Page 11: Connecting A Circulating Pump To The Core Module

    ➥ Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! ❒ Set control of the pump in the relevant menu to “Field pump / PWM” or “Field pump / 0-10V” Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 12 Power connection and wiring Core module and connection options High efficiency pump without control signal It is not possible to control the speed when using this type of pump. The use of a line regulating valve (e.g.: Setter balancing valve) is recommended. 21 11 24 14 22 12...
  • Page 13: Connecting An Isolating Valve To The Core Module

    ❒ Phase (L) for switching the valve and connecting neutral conductor (N) to output “Pump 1” with the RC element ❒ Phase (L) for continuous supply (switches the valve back to the initial position) at output “HCP0” – connect terminal “L1” Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 14: Heating Circuit Pump 0 / Burner Relay

    Power connection and wiring Core module and connection options 2.1.7 Heating circuit pump 0 / burner relay Depending on the system setting, the connection “Heating circuit pump 0” can be used for heating circuit pump 0 or as a burner relay. The following connection instructions must be observed: Heating circuit pump 0 Burner relay The pump can be supplied with up to a...
  • Page 15: Expansion Modules

    Mixing valve 1 Connection cable 4 x 0.75 mm , max. 0.15A / 230V HE-12 Mixing valve 2 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 16: Hydraulic Module

    (storage tank, DHW tank etc.). When using the S1 Turbo firewood boiler, the S4 Turbo, and the S4e Turbo with the Lambdatronic S 3200 control, a hydraulic module is included in the delivery as standard (address 0). A further seven modules (addresses 1 to 7) can be retrofitted.
  • Page 17 Example: Module address “2” = sensor 2.1 to sensor 2.6 HY-13 Mains Connection cable 3 x 1.5 mm , fuse 10A HY-14 Pump _.1 Connection cable 3 x 1.5 mm , max. 1.5A / 230V / 280W Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 18: Connecting A Circulating Pump To The Hydraulic

    Power connection and wiring Expansion modules Connection / Name Note Pump outlets on board. The correct pump designation is determined by the set HY-15 Pump _.2 module address (0-7). Example: module address “2” = pump 2.1 and pump 2.2 Depending on the type of pump, the phase (L) is either connected to the relay output or triac output.
  • Page 19 ❒ Hydraulic module FRHYU22: Connect the power supply for the pump to output "Pump 1" or “Pump 2” and use the triac output for phase (L) ❒ In the relevant menu, set the pump to “Pump without control signal” Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 20 Power connection and wiring Expansion modules High efficiency pump with control signal and release contact When using a high efficiency pump that requires a release contact in addition to the control signal (e.g. Grundfos Magna 3), the pump outlet of the hydraulic module is used to switch the release. up to hydraulic module version FRHYU21 21 11 24 14...
  • Page 21: Connecting An Isolating Valve To The Hydraulic

    “Pump 1” or “Pump 2” using the relay output for phase (L) ❒ Connect the phase (L) for continuous supply (switches the valve back to the initial position) to the power supply at terminal “L” Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 22: Return Mixer Module

    Power connection and wiring Expansion modules 2.2.3 Return mixer module The return mixer module provides the connection for a return mixer. The relevant sensor is the return feed sensor on the core module. If this module is used, the “Return mixer through external mixer module”...
  • Page 23: Ignition Expansion

    2 x 0.75 mm², 24V looping through ZE-06 Core module Use the supplied ribbon cable 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Fuses 10 AT Ignition Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 24 Power connection and wiring Expansion modules Connection diagram Lock Lock Use the network cable provided for connecting to the terminal block Core module Hydraulic module Power supply Mains plug Main switch Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 25: Analogue Module

    Thermocouple Use sensor connection 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Standard configuration – Analogue module with address 0 Input Designation External power specification (0-10V) Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 26: External Power Demand

    Power connection and wiring Expansion modules External power demand The type of power demand can be set using the “Source for ext. power demand (0 – off, 1 – 0-10 V, 2 – modbus)” parameter. The percentages are transferred directly if the power demand is made via modbus.
  • Page 27: Bus Connection

    As the control units are supplied with voltage in addition to transferring data, problems caused by voltage drops can occur depending on the number of modules and existing cable lengths. A voltage supply unit must be used for every touch room console (heating circuit module, hydraulic module). Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 28: Connecting The Bus Cable

    Power connection and wiring BUS connection 2.3.1 Connecting the bus cable For the bus connections between the individual modules, cable type LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be carried out according to the following diagram: Braided shield Braided shield white...
  • Page 29: Setting The Module Address

    For further module types rising module addresses (address 1 - 7) are set. When using the S1 Turbo firewood boiler, the S4 Turbo, and the S4e Turbo with the Lambdatronic S 3200 control, a hydraulic module is included in the delivery as standard (address 0). A further seven modules (addresses 1 to 7) can be retrofitted.
  • Page 30: Potential Equalisation / Potential Separation

    Power connection and wiring BUS connection 2.3.4 Potential equalisation / potential separation There can be potential shifts between buildings. In this case, equalising currents flow via the bus connection shield which can damage the modules. To prevent this, buildings must be connected using a potential equalisation conductor. BUS connection Expansion module...
  • Page 31: Connection Information According To Pump Types

    Connect the control cable to the PDM output on the board, making sure that the polarity is correct: - brown wire to earth - white wire to plus Do not use the other two wires (blue, black) and insulate Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 32: Initial Start-Up With Settings Wizards

    Initial start-up with settings wizards Before switching on for the first time 3 Initial start-up with settings wizards 3.1 Before switching on for the first time NOTICE You should have the initial startup carried out by the authorised heating engineer from Froling customer services.
  • Page 33: General Information About The Settings Wizard

    Connect Setting parameters required for the boiler to use the “froeling-connect.com” online control (IP address, display password, etc.) Heating up program Activation and selection of a heating up program. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 34: Switching On For The First Time

    Initial start-up with settings wizards Switching on for the first time 3.3 Switching on for the first time Once you have connected the device to the power supply and switched on the main switch, the display begins with a query regarding the basic settings of the system (language, production number of the boiler system, date, and time).
  • Page 35: Starting The Setting Wizard

    3: Tap the icon of the settings wizard 4: Tap the “Boiler” setting wizard 5: The settings wizard loads 6: Read the information text and continue with “YES” to start Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 36 Initial start-up with settings wizards Starting the setting wizard Navigation as well as sensor and pump settings Number Description If the Info button has a blue background, more information is available for this overview page. Progress bar for the respective settings wizards Cancel setting wizard Setting the address to which the respective sensor was connected Setting the address to which the respective pump was connected...
  • Page 37: Parameters Overview

    Heating circuit remains in setback mode until another mode is activated Party: Party mode; the current or next setback phase is ignored OFF: Switched off; heating circuit deactivated, only frost protection! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 38: Heating - Temperatures

    Parameters overview Heating 4.1.2 Heating – Temperatures System menu Heating Desired room temperature during heating mode Reduction of flow temperature in setback mode Prerequisite: Heating circuit used in conjunction with The flow temperature is reduced by this value during remote control setback mode.
  • Page 39: Heating - Times

    Here you can set the mixer runtime of the mixer in use. ▪ 0 = boiler NOTICE! To avoid mixer vibration, do not set value < ▪ 1 = buffer tank 01, … 150s! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 40: Heating - Heating Up Program

    Parameters overview Heating High temperature requirement because of DHW tank High temperature requirement because of DHW tank loading loading The DHW tank can be loaded via the heating circuit. If IMPORTANT! Parameter only available for heating circuit there is a requirement from the DHW tank and the criteria 1 and 2! for DHW tank loading have been met, the switch valve Set Pellet as the unit model for “DHW tank 1”...
  • Page 41: Heating Up Programs

    If only 2 heating circuits are installed, then only 2 heating circuits will be available for selection. The heating up program selected will be used for all heating circuits! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 42: Heating - General Settings

    Parameters overview Heating 4.1.6 Heating - General settings System menu Heating General settings service Correction value for external sensor Using room sensor inputs for room thermostat If a deviation of the outside temperature is determined NOTICE! This parameter influences all sensor connections from the evaluated value to the displayed value, the to which an analogue room temperature sensor can be evaluation of the outside temperature sensor can be...
  • Page 43: Water

    If the boiler temperature is above the current DHW tank temperature by this value and the time window is active, DHW tank loading starts (only for systems without a storage tank). Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 44: Water - Times

    Parameters overview Water 4.2.3 Water - Times System menu Water ⇨ See "Setting times" [page 91] 4.2.4 Water - Service System menu Water DHW tank 1 pump will be controlled from HCP0 Legionella heating activated Prerequisite: Hydraulic system for S3 Turbo ▪...
  • Page 45: Solar

    Display of the current speed of the pump between heat Todays yield [kWh] exchanger and buffer tank. Display of the heat quantity that has been supplied by the solar panel system today. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 46: Solar - Temperatures

    Parameters overview Solar Pump between heat exchanger and DHW tank Diverter valve for top/bottom coils Prerequisite: Hydraulic system 12 Prerequisite: Hydraulic system 12 or 13 Display of the current speed of the pump between heat Current control of the isolating valve on the solar side. exchanger and DHW tank.
  • Page 47: Solar - Times

    Maximum collector pump speed If you need to limit the maximum speed of the collector pump for systemic reasons, you can do so by adjusting this parameter. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 48 Parameters overview Solar For solar to store and DHW tank, the DHW tank has Control of storage tank – heat exchanger pump priority Prerequisite: Hydraulic system 12 or 13 ▪ YES: The DHW tank is loaded until the temperature set Definition of control signal for pump type used.
  • Page 49: Solar - Heat Meter

    Is an external flow through counter used Shows the historical progression of the solar panel system. ▪ YES: An external volume pulse transmitter is in use. The yields of the last 6 days are available. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 50: Buffer Tank

    Parameters overview Buffer tank 4.4 Buffer tank 4.4.1 Buffer tank - Status System menu Buffer tank Buffer tank top temperature Buffer tank bottom temperature Display of the current temperature in the top part of the Display of the current temperature in the lower part of the buffer tank.
  • Page 51: Buffer Tank - Temperatures

    Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 52: Buffer Tank - Service

    Parameters overview Buffer tank 4.4.3 Buffer tank - Service System menu Buffer tank Enable heating circuit pump 0 according to top buffer Pump output of storage tank pump temp. Pump outlet to which the buffer loading pump is ▪ NO: Release of heating circuit pump 0 according to the connected.
  • Page 53: Boiler

    Display of the current value of the primary air flap according to controller. Position of primary air flap Display of the current position of the primary air flap (adjusted for the air settings). Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 54: Boiler - Temperatures

    Parameters overview Boiler 4.5.2 Boiler - Temperatures System menu Boiler Boiler temperature setpoint Minimum boiler temperature to release all pumps The boiler temperature is regulated to this temperature. When the current boiler temperature reaches this value, Setting range 70 – 90°C the storage tank loading pump starts (hysteresis: 2°C).
  • Page 55: Boiler - General Settings

    SD card. This Designed to invert the input signal (0V = 0% ➾ 0V = parameter specifies at what intervals the recording should 100%). be started. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 56: Boiler - General Settings - Modbus Settings

    Parameters overview Boiler Input external power demand EEPROM reset Current input value for the external power demand. ▪ YES: All boiler settings and system configurations are deleted. The boiler is only functional again once it has Current external power demand been recommissioned by Froling customer services or authorized installer.
  • Page 57: Boiler - General Settings - Operator Data

    Standby boiler pump ▪ ON: Secondary boiler is activated immediately Prerequisite: “Switch valve installed” parameter NOTICE! Burner blockage noted. set to “NO” Display of the current pump control for the standby boiler. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 58: Boiler 2 - Temperatures

    Parameters overview Boiler 2 4.6.2 Boiler 2 - Temperatures System menu Boiler 2 Secondary boiler start delay Maximum outfeed temperature for heat pump operation If there is a requirement from the heating circuit or DHW Prerequisite: Heat pump as standby boiler tank and the buffer tank or boiler has insufficient If a flow temperature higher than the set value is required, temperature, the secondary boiler starts after the specified...
  • Page 59: Boiler 2 - Service

    Control of boiler 2 pump Definition of control signal for pump type used. ⇨ See "Activation options of pump outlets" [page 85] Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 60: Ignition

    Parameters overview Ignition 4.7 Ignition System menu Ignition Automatic ignition Ignition time (date - time) process starts if the top storage tank temperature falls ▪ NO: Automatic ignition deactivated below the maximum flow temperature setpoint. The ▪ YES: Automatic ignition activated period applies from the specified time until 24:00 h on the specified date.
  • Page 61: Fuel

    A prompt then appears to confirm whether the selected. A prompt then appears to confirm whether the specified values for the chosen fuel selection should be specified values for the chosen fuel selection should be adopted. adopted. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 62: Network Pump

    Parameters overview Network pump 4.9 Network pump 4.9.1 Network pump - Status System menu Network pump Network return temperature Return temperature distributor 2 … 4 Display of the current return temperature of the remote Prerequisite: Variant 2 or variant 3 and pump for distributor line.
  • Page 63: Network Pump - Service

    Control of distributor 1 pump Prerequisite: Variant 1 and pump for distributor 1 installed Definition of control signal for pump type used. ⇨ See "Activation options of pump outlets" [page 85] Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 64: Difference Regulator

    Parameters overview Difference regulator 4.10 Difference regulator 4.10.1 Difference regulator - Status System menu Diff. control Heat source temperature Pump speed Display of the current heat source temperature of the Specifies the current speed of the differential controller differential controller (e.g. tiled stove with water pocket, pump.
  • Page 65: Difference Regulator - Times

    Maximum pump speed If you need to limit the maximum speed of the pump of the differential controller for systemic reasons, you can do so by adjusting this parameter. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 66: Circulation Pump

    Parameters overview Circulation pump 4.11 Circulation pump 4.11.1 Circulation pump - Status System menu Circ. Pump Return temperature in circulation line Flow switch on the domestic hot water line Display of the current temperature at the return feed ▪ 0: Flow switch detects no flow rate. sensor of the circulation line.
  • Page 67: Circulation Pump - Times

    If you need to limit the maximum speed of the circulation pump for systemic reasons, you can do so by adjusting Pump output of circulation pump this parameter. Pump outlet to which the circulation pump is connected. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 68: Manual

    Parameters overview Manual 4.12 Manual 4.12.1 Manual - Manual operation Manual operation System menu Manual When exiting the “Manual operation” menu, all active parameters are automatically set to “OFF”! The parameters displayed depend on the boiler configuration! Rinse the condenser manually – only possible if boiler off / on standby ▪...
  • Page 69: Manual - Analogue Outputs

    The parameters displayed depend on the boiler configuration! ▪ A 0: Automatic, Off; A 1-100%: Automatic, with % value ▪ 1-100%: Manual, with % value ON ▪ 0%: Manual, Off Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 70: Manual - Digital Inputs

    Parameters overview Manual 4.12.4 Manual - Digital inputs Digital inputs System menu Manual The parameters displayed depend on the boiler configuration! ▪ A 0: Automatic, Off; A 1: Automatic, On ▪ 1: Manual, On ▪ 0: Manual, Off Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 71: System

    Desired work point of flue gas temperature the current boiler temperature must at least exceed the value set here. Flue gas temperature to be maintained in firewood operation under the influence of the boiler control variable. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 72: Setting - Ignition

    Parameters overview System Setting - Ignition Ignition System menu System Setting Automatic ignition Ignition time (date - time) ▪ NO: Automatic ignition deactivated Day (date or daily) and time setting for the start of ignition. The parameter is only active when the “Start ▪...
  • Page 73: Setting - Air Settings

    “0%” and the current flue gas temperature is over “100°C” the safety time starts. If the control of the secondary air flap does not change within this set period of time, a warning appears on the display. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 74: Setting - Lambda Values

    Parameters overview System Setting - Lambda values Lambda values System menu System Setting Residual oxygen content setpoint Residual oxygen above which the lambda probe is allowed to switch off Residual oxygen content which is regulated during “Heating” status. If the boiler switches to “Boiler off” or “Off” mode, the lambda probe heating remains active for at least 1 hour, Residual oxygen content, above which it switches to OFF up to a maximum of 24 hours.
  • Page 75 Display of the measured broadband probe heating voltage. Broadband probe heating current Broadband probe Nernst voltage Display of the measured broadband probe heating current. Display of the measured Nernst voltage of the broadband probe. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 76: Set - Quantity Of Heat Calculation

    Parameters overview System Broadband probe pump current Broadband probe internal resistance Display of the measured broadband probe pump current. Display of the measured internal resistance of the broadband probe. Set - Quantity of heat calculation Flow temperature sensor correction value Litres per pulse of flow sensor If, at the same ambient temperature, the flow temperature If an external volume pulse transmitter is used, adjust this...
  • Page 77: Setting - General Settings

    General settings System menu System Setting ⇨ See "Boiler - General settings" [page 55] MODBUS settings MODBUS General settings settings Setting ⇨ See "Boiler - General settings - MODBUS settings" [page Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 78: System - Current Values

    Parameters overview System 4.13.2 System - Current values System menu System Current values Display of the current value for the relevant parameter. The parameters displayed depend on the boiler configuration! 4.13.3 System - Sensors and pumps System menu System Sensors and pumps In the “Sensors and pumps”...
  • Page 79: Diagnostics

    You can determine what type of fault message it is, when another fault indication entry, the oldest entry will be deleted the fault occurred (appeared), when the fault was to make room for the current one. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 80: Diagnostics - Clear Error History

    Parameters overview Diagnostics 4.14.4 Diagnostics - Clear error history Clear error history System menu Diagnostics The entire error history can be deleted using this function. From this time on, the error history will be filled again with new fault messages. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 81: Touchscreen

    ▪ On: The address in the local network (IP address), the subnet mask, default gateway and DNS server are automatically assigned by the router/server. ▪ Off: IP address, subnet mask, default gateway and DNS server can be manually set. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 82: Display Settings - Basic Display

    Parameters overview Touchscreen Display settings - Basic display Basic display System menu Touchscreen Display settings Figures 1 … 6 On the basic display, up to six different information displays can be freely selected. The selection depends on the system configuration. Display settings - Date / Time Date / Time System menu...
  • Page 83: Touchscreen - Display Operating Rights

    Password for the touchscreen with address 1 … 7 can be NOTICE! The same password can be assigned for each issued. touch display! Password for boiler display Password for boiler display can be issued. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 84: Touchscreen - Display Allocation

    Parameters overview Touchscreen 4.15.3 Touchscreen - Display allocation System menu Touchscreen Display allocations Heating circuit system: DHW tank system: Touch display with address 1 ... 7 is assigned to the Touchscreen with address 1 ... 7 is assigned to the following heating circuit: following DHW tank: To assign a room console to a heating circuit, the...
  • Page 85: Faq

    When set to “Isolating valve” the output is activated either with 0% or 100%. This setting value is only available in the “Water” or “Boiler 2” menu. HKP0 The following applies to pump outlet HKP0 at the core module: ▪ Relay output ▪ Speed control is not possible Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 86: Pump Stall Protection

    Pump stall protection 5.2 Pump stall protection After extended standstill times, there is a risk the pump drive may block due to corrosion and deposits. The pump stall protection feature is intended to prevent this. The control ensures that the circulation pumps are switched on briefly on a regular basis, even outside the season of use.
  • Page 87: Boiler Operating Statuses

    “heating” status. Door open The insulating door is open and the fan runs at maximum speed. The fuel burns down to residual embers. Fault CAUTION - There is a fault! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 88: Determination Of The Quantity Of Heat

    Determination of the quantity of heat 5.4 Determination of the quantity of heat 5.4.1 Assembly Information The contact sensor and the line regulating valve must be positioned in the direction of flow downstream of the circulating pump and immediately upstream of the return connection of the boiler. Additional contact sensors and line regulating valves are required for boilers without return temperature control or return temperature control with thermal valve.
  • Page 89 ❒ Activate the circulating pump in manual operation at 50% speed ❒ Press the push bar on the line regulating valve; make a note of the flow on the scale Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 90: Setting The Type Of Heat Quantity Calculation

    Determination of the quantity of heat Setting the type of heat quantity calculation ❒ In the boiler’s setting wizard, select “Record with pump speed“ Configuring the heat quantity calculation ❒ Go to the menu “System → Settings → Boiler heat quantity calculation” ❒...
  • Page 91: Setting Times

    ❒ Tap the symbol under the day of the week ➥ The edit window will appear You can specify up to four time windows per component and day. ❒ Tap the desired time window Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 92 Setting times ❒ The time window will open for editing ❒ Set the start and end time for the time window using the up and down arrows ❒ Save the time window setting by tapping on the confirm icon If you want to apply the time window setting to another day in addition, you can do this by activating the relevant day.
  • Page 93: Calibrating The Touchscreen

    ➥ The touchscreen will restart and begin calibrating To calibrate the touchscreen, you much press five points indicated by a crosshair in the order shown. The control will restart after calibration. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 94 Calibrating the touchscreen NOTICE Inaccurate calibration If you do not tap the indicated points accurately, the control may stop working properly and a software update may be required. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 95: Software Update Lambdatronic 3200

    ⇨ See "Carrying out a software update on the boiler controller" [page 96] Perform software update of all touch controls USB-C USB-A USB-A ⇨ See "Carrying out a software update on the touch control" [page 98] Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 96: Carrying Out A Software Update On The Boiler Controller

    Software update Lambdatronic 3200 Close Flash Update Wizard - restart controller Lambdatronic Service ⇨ See "Finishing a software update" [page 99] 5.7.1 Carrying out a software update on the boiler controller Selecting a Flash file Once the connection has been established, the main window displays the update files which can be installed: ▪...
  • Page 97 When the flash update is successfully transferred to the boiler controller, the following window appears: NOTICE! Do not close the update at this time and do not disconnect the boiler controller! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 98: Carrying Out A Software Update On The Touch Control

    Software update Lambdatronic 3200 5.7.2 Carrying out a software update on the touch control NOTICE! If several touch controls are installed, we recommend the use of several USB sticks to perform the updates in parallel! ❒ Insert the USB stick with the necessary data (linux.bin; rootfs.img; update; froresetdemo.inc or frorestart.inc) into the USB port ➥...
  • Page 99: Finishing A Software Update

    ➥ After restarting the boiler controller, check whether all touch controls have started up correctly NOTICE! If not all touch controls connect to the boiler control, a restart of the entire system (main switch OFF/ ON) is necessary! Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 100: Usb Data Recording

    USB data recording 5.8 USB data recording ❒ Switch off the boiler using the main switch ❒ Remove the insulating cover and disassemble the retaining brackets on the rear of the display bracket ❒ Push the display to the right until pin (A) is positioned on the left outside the holding fixture ❒...
  • Page 101 ➥ The USB must not contain a software update ➥ Recording starts automatically once the touch display has started Data recording is indicated in the status line by means of the USB symbol with an activity bar. Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 102: Notes

    Notes 6 Notes Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
  • Page 103 Notes Service manual Lambdatronic S 3200 for firewood boiler | B1420922_en...
  • Page 104: Appendix

    Appendix Addresses 7 Appendix 7.1 Addresses 7.1.1 Address of manufacturer FRÖLING Heizkessel- und Behälterbau GesmbH Industriestraße 12 A-4710 Grieskirchen AUSTRIA TEL 0043 (0)7248 606 0 FAX 0043 (0)7248 606 600 EMAIL info@froeling.com INTERNET www.froeling.com Customer service Austria 0043 (0)7248 606 7000 Germany 0049 (0)89 927 926 400 Worldwide...