Air-cooled liquid chillers and reversible heat pumps (44 pages)
Summary of Contents for MTA TAEevo015
Page 1
Painting systems & machines 2FC IMPIANTI SRL Via G. Marconi 20/1 35010 Villanova di CSP (PD) - Italia 1.5.1 Water chillers Water chillers...
Page 2
ATER HILLERS TAEevo015÷351 MAINTENANCE AND OPERATING MANUAL 38178800500 Original instructions...
Page 4
Symbols and leds on the display ..................... 24 Remote terminal ........................24 7.4.1 Function of buttons ..........................24 TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 5
11.1.9 Alarm parameters .............................40 11.1.10LASER parameters (NOT ENABLED FUNCTION) ................40 ................................41 ALARMS 12.1 Alarm codes and actions ......................41 12.2 Outlet blocking.........................44 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Water filling point Air vent Hole for inserting bars for lifting the machine Table 1 S YMBOLS TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 7
MODEL and MACHINE NUMBER shown on the machine data plate and on the first page of this manual. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 8
Arbitrary modifications made to the unit will automatically invalidate all forms of guarantee provided by the manufacturer. ATTENTION The hot / cold water produced by MTA units cannot be used directly for domestic hygiene or food applications. In the case of such applications, the installer is responsible for fitting an intermediate exchanger.
Page 9
(with steam, for example), before carrying out these operations. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 10
HANDLING AND STORAGE Handling technical measures/ precautions: Ensure sufficient air change and/or extraction in the work areas. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Global warming potential HGWP (R11=1): R125: 0.84 - R134a: 0.28 Ozone depletion potential ODP (R11=1): CONSIDERATIONS ON DISPOSAL Usable with reconditioning. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
O t h e r d a t a r e l a t i v e t o t h e s t a n d a r d m a c h i n e s 3 . 1. 1 Di me n si o n s See enclosures. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 13
460/3/60 Hz supply) total air flow 59438 56268 80132 77490 88695 88695 (gpm) Table 5 C HARACTERISTICS OF STANDARD UNITS TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 14
(5,2 FT) from the ground. Values tolerance ± 2 dB. Sound power level: in compliance with ISO 3744 TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 15
MAINTENANCE AND OPERATING MANUAL Chapter 3 - Technical data TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 16
(in models without prismatic tank present only from TAEevo031); • dryer filter; • liquid flow sight glass (in models without prismatic tank present only from TAEevo031); • lamination capillary (only for TAEevo015÷020); • refrigerant manometers (TAEevo031); • Schrader service valves; Consult the enclosed drawings for additional information.
Page 17
The protection rating of the fans is IP54. The protection rating of the fans is IP44 for TAEevo015÷020. All fans have “F” insulation class to assure the external working with all types of climates. The assembly is completed with a superior (support to the fan) safety protection grill.
Page 18
The pump and tank can be equipped with electrical heaters to prevent icing up (instead of using glycol solutions). TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 19
MAINTENANCE AND OPERATING MANUAL Chapter 4 - Description TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Carry out the level sensor calibration when the unit is activated the first time. Repeat the operation each time the composition of the process liquid changes. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 21
The non-observance of this prescription can cause big damages to the evaporator. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 22
30(86) 0,9936 1,0067 1,0199 1,033 1,0461 40(104) 0,9905 1,003 1,0156 1,0282 1,0408 Table 8 S PECIFIC WEIGHTS TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 23
PVC insulation from 70°C (if not specified) or EPR insulation from 90°C Consult the enclosed electrical diagram for additional information. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 24
When SET-POINT value has been reached, the electronic control controlling the water inlet temperature stops the compressor. The water pump, on the other hand, is always in motion. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 25
MAINTENANCE AND OPERATING MANUAL Chapter 6 - Start up TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 26
During programming phase it selects a parameter of confirms a value. It allows to enter Function Menu. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 27
/ pressure. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 28
6. To exit the procedure: Press when a parameter is displayed, or wait (about 240 seconds) without pressing any button. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 29
Also in stand-by modality the controller can: 1. Display the measured values 2. Manage the alarms by displaying and signalling. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 30
7. If the password is correct the Label “ArSt” flashes for 5 seconds to confirm the resetting. After resetting the unit returns to normal displaying. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 31
-BCP1 CONDENSING PRESSURE TRANSDUCER (only with electronic regulation) -BAT1 AMBIENT AIR TEMPERATURE PROBE (Only with antifreeze protection function) TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Com pres s o r reg u la tio n g ra phi c i n C h il le r m ode With 1 compressor With 2 compressors ST09 = 2 TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 33
The following graphic shows the progress of the fan rotation speed according to the condensing pressure changings. % of rotation speed Vmax Vmin P min P max condensing pressure [bar g] TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 34
If the electrical resistance of the liquid is outside the maximum range of the control device, green LED (3) will flash rapidly for 2 seconds while amber LED (2) remains off, thus signalling a teach-in error. ATTENTION The level sensor has been calibrated by MTA to operate at maximum sensitivity admissible on the instrument (220kOhm). Modifications to this setting may impair correct operation. TAEevo015÷351 TAEevo015÷351...
Page 35
MAINTENANCE AND OPERATING MANUAL Chapter 8 - Other components setting TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
(F) or the side panels (D), (E), (G) or (H). TAEevo 015÷020 TAEevo 031÷161 TAEevo 201÷351 TAEevo 201÷351 TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 37
- This plan is based on an average working situation. - In some installations it may be necessary to increase the frequency of maintenance. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
(units without hydraulic • main alarm relay tripped. again (chapter Electronic kit). Board). TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 39
The refrigerant fluid is scroll compressor is wrong not compressed and the (only three-phase units). unit doesn’t cool. TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 40
• EE flashes on the display; • the led of general alarm icon lights up. TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 41
MAINTENANCE AND OPERATING MANUAL Chapter 10 - Trouble shooting TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
5 = unit status (**) • 6 = Laser set • 7 = none • 8 = operating differential TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 43
1 1 .1 . 1 0 L A S E R p a r a m e t e r s ( N O T E N A B L E D F U N C T I O N ) Parameter Level Description Min. Max. Resolution Factory setting Password TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 44
Disabled if BAT1 > than “set value” and the The alarm code is displayed resetting procedure is carried out TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 45
PB2 is The buzzer is activated lower than AL23 The alarm code is displayed TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 46
(reset procedure in function menu). It is memorized in the alarm historic only with manual rearm TAEevo015÷351 TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.
Page 47
The electronic control board is furnished with a “history” loop, see chapter 7.12.5 “How to display the alarm historic “ALoG”” . TAEevo015÷351 The data inside this manual are not binding and they can be modified by the manufacturer without notice. All rights reserved.