Toshiba TOSVERT VF-A5 Instruction Manual page 44

High-performance inverter
Hide thumbs Also See for TOSVERT VF-A5:
Table of Contents

Advertisement

E6580516
(3)
Status alarms
Alarm characters and the frequency setting may be alternately displayed on the LED in standard
monitor mode. The following four types of characters may be displayed.
C
···When current exceeding the overcurrent stall level flows.
P
···When voltage exceeding the overvoltage stall level is generated.
L
···When 50% or more of the overload trip value is reached.
H
···When the temperature reaches the overheat protection alarm setting level.
Several alarms may also be displayed simultaneously.("
LC
11
11
PC "
11
L PC
11
)
The alarms will automatically go out when the alarm condition is removed.
(4) Trip information
The standard monitor mode trip display will be entered immediately when a trip occurs.
Display
Explanation
,-, ,-
'
Overcurrent during acceleration
wr_
I
0[2
Overcurrent during deceleration
0[3
Overcurrent during constant-speed run
,-,
,-
IP
DC section overcurrent during acceleration
wr_
OC2P
DC section overcurrent during deceleration
OC3P
DC section overcurrent during constant speed run
,-, , - I
Load-end short circuit (output terminal check) trip during start-up
,_,
,_ ,_
oc.c:
I
U-phase short circuit
I
OCA2
V-phase short circuit
oc.c:3
W-phase short circuit
OP
I
Overvoltage during acceleration
I
0F'2
Overvoltage during deceleration
OP3
Overvoltage during constant-speed run
,-, I
:
,-,
Inverter overload trip
,_,
,_
,-,
'
,-,
,_
wr_
'·~
Motor overload trip
oc.-
Dynamic braking resistor overcurrent trip
OL.-
Dynamic braking resistor overload trip
0:-1
Overheat trip
EFU
DC fuse cut
E
Emergency stop
EEP
,
EEPROM fault (write error)
I
EEP2
Initial read fault
E.-,-2
RAM fault
E.-,- 3
ROM fault
E ,- .-
'-I
CPU error trip
E,-,-5
Communication interruption error
E.-,-5
Gate array fault
E.-,-'1
Output current detector fault
E.-,-8
Option PCB fault trip
E.-,-9
Optional ROM drop-off error
I
I,..
Low-current operating condition trip
wr_
UP '
Undervoltage trip (main circuit)
I
Of=
Overtorque trip
EF
,
or
EF2
Earth-fault trip
I
El=,-,
Auto-tuning error
EI:: '=IP
Inverter typeform error (Special
error,
refer to page 42. )
,-,E ,- ,-
No error (Refer to past trip display on page
35.
)
The inverter status at the time of the saved trips (trips that previously occurred) can also be read.
(Refer to Status monitor mode on page 40. )